⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.99V (1.46%)
Voltage at Load End474.4 VLoss: 5.65 V (4647.4 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1032.0 V (215.0%)0.0 V1702.32 V (354.65%)849051.2 WDrop/Amp High
12 AWG3.31 mm²20 A648.51 V (135.11%)0.0 V1069.73 V (222.86%)533542.7 WDrop/Amp High
10 AWG5.26 mm²30 A408.09 V (85.02%)71.9 V673.16 V (140.24%)335746.5 WDrop/Amp High
8 AWG8.37 mm²50 A256.46 V (53.43%)223.5 V423.04 V (88.13%)210994.8 WDrop/Amp High
6 AWG13.3 mm²65 A161.4 V (33.62%)318.6 V266.23 V (55.46%)132783.9 WDrop/Amp High
4 AWG21.15 mm²85 A101.49 V (21.14%)378.5 V167.41 V (34.88%)83500.1 WDrop/Amp High
3 AWG26.67 mm²100 A80.49 V (16.77%)399.5 V132.76 V (27.66%)66217.7 WDrop/Amp High
2 AWG33.62 mm²115 A63.85 V (13.3%)416.2 V105.32 V (21.94%)52529.0 WDrop/Amp High
1 AWG42.41 mm²130 A50.61 V (10.54%)429.4 V83.49 V (17.39%)41641.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.13 V (8.36%)439.9 V66.2 V (13.79%)33016.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.83 V (6.63%)448.2 V52.51 V (10.94%)26190.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.25 V (5.26%)454.7 V41.65 V (8.68%)20774.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.02 V (4.17%)460.0 V33.03 V (6.88%)16474.1 WDrop/Amp High
250 kcmil126.7 mm²255 A16.94 V (3.53%)463.1 V27.95 V (5.82%)13938.6 WDrop/Amp High
300 kcmil152.0 mm²285 A14.12 V (2.94%)465.9 V23.29 V (4.85%)11618.6 WDrop/Amp High
350 kcmil177.3 mm²310 A12.11 V (2.52%)467.9 V19.97 V (4.16%)9960.7 WDrop/Amp High
400 kcmil202.7 mm²335 A10.59 V (2.21%)469.4 V17.47 V (3.64%)8712.5 WDrop/Amp High
500 kcmil253.4 mm²380 A8.47 V (1.76%)471.5 V13.97 V (2.91%)6969.3 WDrop/Amp High
600 kcmil304.0 mm²420 A7.06 V (1.47%)472.9 V11.65 V (2.43%)5809.3 WDrop/Amp High
750 kcmil380.0 mm²475 A5.65 V (1.18%)474.4 V9.32 V (1.94%)4647.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.24 V (0.88%)475.8 V6.99 V (1.46%)3485.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 400 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.65V (1.18%) and delivers 474.4V at the load.

What size aluminum wire is required for 475 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.99V (1.46%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.