🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.65%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.86V (3.28%)
Voltage at Load End233.6 VLoss: 6.35 V (5228.4 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1161.0 V (483.75%)0.0 V1915.11 V (797.96%)955182.6 WDrop/Amp High
12 AWG3.31 mm²20 A729.57 V (303.99%)0.0 V1203.45 V (501.44%)600235.6 WDrop/Amp High
10 AWG5.26 mm²30 A459.1 V (191.29%)0.0 V757.3 V (315.54%)377714.8 WDrop/Amp High
8 AWG8.37 mm²50 A288.52 V (120.22%)0.0 V475.92 V (198.3%)237369.1 WDrop/Amp High
6 AWG13.3 mm²65 A181.57 V (75.65%)58.4 V299.51 V (124.79%)149381.9 WDrop/Amp High
4 AWG21.15 mm²85 A114.18 V (47.57%)125.8 V188.34 V (78.48%)93937.6 WDrop/Amp High
3 AWG26.67 mm²100 A90.55 V (37.73%)149.5 V149.36 V (62.23%)74494.9 WDrop/Amp High
2 AWG33.62 mm²115 A71.83 V (29.93%)168.2 V118.48 V (49.37%)59095.2 WDrop/Amp High
1 AWG42.41 mm²130 A56.94 V (23.73%)183.1 V93.93 V (39.14%)46847.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A45.15 V (18.81%)194.9 V74.47 V (31.03%)37143.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.81 V (14.92%)204.2 V59.07 V (24.61%)29464.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A28.41 V (11.84%)211.6 V46.86 V (19.52%)23371.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.53 V (9.39%)217.5 V37.16 V (15.48%)18533.4 WDrop/Amp High
250 kcmil126.7 mm²255 A19.06 V (7.94%)220.9 V31.44 V (13.1%)15681.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.89 V (6.62%)224.1 V26.21 V (10.92%)13070.9 WDrop/Amp High
350 kcmil177.3 mm²310 A13.62 V (5.68%)226.4 V22.47 V (9.36%)11205.8 WDrop/Amp High
400 kcmil202.7 mm²335 A11.91 V (4.96%)228.1 V19.65 V (8.19%)9801.6 WDrop/Amp High
500 kcmil253.4 mm²380 A9.53 V (3.97%)230.5 V15.72 V (6.55%)7840.5 WDrop/Amp High
600 kcmil304.0 mm²420 A7.94 V (3.31%)232.1 V13.1 V (5.46%)6535.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.35 V (2.65%)233.6 V10.48 V (4.37%)5228.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.77 V (1.99%)235.2 V7.86 V (3.28%)3921.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 450 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.35V (2.65%) and delivers 233.6V at the load.

What size aluminum wire is required for 475 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.86V (3.28%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.