🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.86V (1.64%)
Voltage at Load End473.6 VLoss: 6.35 V (5228.4 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1161.0 V (241.87%)0.0 V1915.11 V (398.98%)955182.6 WDrop/Amp High
12 AWG3.31 mm²20 A729.57 V (151.99%)0.0 V1203.45 V (250.72%)600235.6 WDrop/Amp High
10 AWG5.26 mm²30 A459.1 V (95.65%)20.9 V757.3 V (157.77%)377714.8 WDrop/Amp High
8 AWG8.37 mm²50 A288.52 V (60.11%)191.5 V475.92 V (99.15%)237369.1 WDrop/Amp High
6 AWG13.3 mm²65 A181.57 V (37.83%)298.4 V299.51 V (62.4%)149381.9 WDrop/Amp High
4 AWG21.15 mm²85 A114.18 V (23.79%)365.8 V188.34 V (39.24%)93937.6 WDrop/Amp High
3 AWG26.67 mm²100 A90.55 V (18.86%)389.5 V149.36 V (31.12%)74494.9 WDrop/Amp High
2 AWG33.62 mm²115 A71.83 V (14.96%)408.2 V118.48 V (24.68%)59095.2 WDrop/Amp High
1 AWG42.41 mm²130 A56.94 V (11.86%)423.1 V93.93 V (19.57%)46847.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A45.15 V (9.41%)434.9 V74.47 V (15.51%)37143.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.81 V (7.46%)444.2 V59.07 V (12.31%)29464.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A28.41 V (5.92%)451.6 V46.86 V (9.76%)23371.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.53 V (4.69%)457.5 V37.16 V (7.74%)18533.4 WDrop/Amp High
250 kcmil126.7 mm²255 A19.06 V (3.97%)460.9 V31.44 V (6.55%)15681.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.89 V (3.31%)464.1 V26.21 V (5.46%)13070.9 WDrop/Amp High
350 kcmil177.3 mm²310 A13.62 V (2.84%)466.4 V22.47 V (4.68%)11205.8 WDrop/Amp High
400 kcmil202.7 mm²335 A11.91 V (2.48%)468.1 V19.65 V (4.09%)9801.6 WDrop/Amp High
500 kcmil253.4 mm²380 A9.53 V (1.99%)470.5 V15.72 V (3.27%)7840.5 WDrop/Amp High
600 kcmil304.0 mm²420 A7.94 V (1.65%)472.1 V13.1 V (2.73%)6535.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.35 V (1.32%)473.6 V10.48 V (2.18%)5228.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.77 V (0.99%)475.2 V7.86 V (1.64%)3921.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 450 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.35V (1.32%) and delivers 473.6V at the load.

What size aluminum wire is required for 475 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.86V (1.64%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.