🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.66%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.1V (5.46%)
Voltage at Load End236.0 VLoss: 3.97 V (3267.5 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1935.0 V (806.25%)0.0 V3191.85 V (1329.94%)1591970.9 WDrop/Amp High
12 AWG3.31 mm²20 A1215.95 V (506.65%)0.0 V2005.75 V (835.73%)1000392.6 WDrop/Amp High
10 AWG5.26 mm²30 A765.17 V (318.82%)0.0 V1262.17 V (525.91%)629524.6 WDrop/Amp High
8 AWG8.37 mm²50 A480.86 V (200.36%)0.0 V793.19 V (330.5%)395615.2 WDrop/Amp High
6 AWG13.3 mm²65 A302.62 V (126.09%)0.0 V499.18 V (207.99%)248969.9 WDrop/Amp High
4 AWG21.15 mm²85 A190.3 V (79.29%)49.7 V313.9 V (130.79%)156562.6 WDrop/Amp High
3 AWG26.67 mm²100 A150.91 V (62.88%)89.1 V248.93 V (103.72%)124158.2 WDrop/Amp High
2 AWG33.62 mm²115 A119.71 V (49.88%)120.3 V197.47 V (82.28%)98492.0 WDrop/Amp High
1 AWG42.41 mm²130 A94.9 V (39.54%)145.1 V156.54 V (65.23%)78078.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A75.24 V (31.35%)164.8 V124.12 V (51.72%)61905.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A59.69 V (24.87%)180.3 V98.46 V (41.02%)49107.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A47.35 V (19.73%)192.7 V78.1 V (32.54%)38951.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A37.54 V (15.64%)202.5 V61.93 V (25.8%)30889.0 WDrop/Amp High
250 kcmil126.7 mm²255 A31.77 V (13.24%)208.2 V52.4 V (21.83%)26135.0 WDrop/Amp High
300 kcmil152.0 mm²285 A26.48 V (11.03%)213.5 V43.68 V (18.2%)21784.9 WDrop/Amp High
350 kcmil177.3 mm²310 A22.7 V (9.46%)217.3 V37.45 V (15.6%)18676.3 WDrop/Amp High
400 kcmil202.7 mm²335 A19.86 V (8.27%)220.1 V32.75 V (13.65%)16336.0 WDrop/Amp High
500 kcmil253.4 mm²380 A15.88 V (6.62%)224.1 V26.2 V (10.92%)13067.5 WDrop/Amp High
600 kcmil304.0 mm²420 A13.24 V (5.52%)226.8 V21.84 V (9.1%)10892.4 WDrop/Amp High
750 kcmil380.0 mm²475 A10.59 V (4.41%)229.4 V17.47 V (7.28%)8713.9 W~ ≤5%
1000 kcmil506.7 mm²545 A7.94 V (3.31%)232.1 V13.1 V (5.46%)6535.0 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 750 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.97V (1.66%) and delivers 236.0V at the load.

What size aluminum wire is required for 475 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.1V (5.46%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.