🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 450 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 0.32V (2.65%)
Voltage at Load End11.7 VLoss: 0.35 V (1.7 W)
Power & Breaker (125%)0.06 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 450 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A14.11 V (117.6%)0.0 V23.28 V (193.98%)70.6 WDrop/Amp High
12 AWG3.31 mm²20 A8.87 V (73.9%)3.1 V14.63 V (121.9%)44.3 WDrop/Amp High
10 AWG5.26 mm²30 A5.58 V (46.5%)6.4 V9.2 V (76.71%)27.9 WDrop/Amp High
8 AWG8.37 mm²50 A3.51 V (29.22%)8.5 V5.78 V (48.21%)17.5 WDrop/Amp High
6 AWG13.3 mm²65 A2.21 V (18.39%)9.8 V3.64 V (30.34%)11.0 WDrop/Amp High
4 AWG21.15 mm²85 A1.39 V (11.57%)10.6 V2.29 V (19.08%)6.9 WDrop/Amp High
3 AWG26.67 mm²100 A1.1 V (9.17%)10.9 V1.82 V (15.13%)5.5 WDrop/Amp High
2 AWG33.62 mm²115 A0.87 V (7.28%)11.1 V1.44 V (12.0%)4.4 WDrop/Amp High
1 AWG42.41 mm²130 A0.69 V (5.77%)11.3 V1.14 V (9.51%)3.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A0.55 V (4.57%)11.5 V0.91 V (7.54%)2.7 W~ ≤5%
2/0 AWG67.43 mm²175 A0.44 V (3.63%)11.6 V0.72 V (5.98%)2.2 W~ ≤5%
3/0 AWG85.01 mm²200 A0.35 V (2.88%)11.7 V0.57 V (4.75%)1.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.27 V (2.28%)11.7 V0.45 V (3.76%)1.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.23 V (1.93%)11.8 V0.38 V (3.18%)1.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.19 V (1.61%)11.8 V0.32 V (2.65%)1.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.17 V (1.38%)11.8 V0.27 V (2.28%)0.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (1.21%)11.9 V0.24 V (1.99%)0.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.12 V (0.97%)11.9 V0.19 V (1.59%)0.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.1 V (0.8%)11.9 V0.16 V (1.33%)0.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.08 V (0.64%)11.9 V0.13 V (1.06%)0.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.06 V (0.48%)11.9 V0.1 V (0.8%)0.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 450 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 450 feet one-way at 12V (DC), you need 3/0 AWG copper wire. This produces a voltage drop of 0.35V (2.88%) and delivers 11.7V at the load.

What size aluminum wire is required for 5 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 0.32V (2.65%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.