🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.67%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.55V (2.19%)
Voltage at Load End206.6 VLoss: 1.38 V (1314.2 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A672.16 V (323.15%)0.0 V1108.75 V (533.05%)640316.3 WDrop/Amp High
12 AWG3.31 mm²20 A422.38 V (203.07%)0.0 V696.73 V (334.97%)402374.0 WDrop/Amp High
10 AWG5.26 mm²30 A265.8 V (127.79%)0.0 V438.44 V (210.79%)253204.9 WDrop/Amp High
8 AWG8.37 mm²50 A167.04 V (80.31%)41.0 V275.53 V (132.47%)159122.8 WDrop/Amp High
6 AWG13.3 mm²65 A105.12 V (50.54%)102.9 V173.4 V (83.36%)100139.7 WDrop/Amp High
4 AWG21.15 mm²85 A66.1 V (31.78%)141.9 V109.04 V (52.42%)62972.0 WDrop/Amp High
3 AWG26.67 mm²100 A52.42 V (25.2%)155.6 V86.47 V (41.57%)49938.4 WDrop/Amp High
2 AWG33.62 mm²115 A41.59 V (19.99%)166.4 V68.6 V (32.98%)39615.0 WDrop/Amp High
1 AWG42.41 mm²130 A32.97 V (15.85%)175.0 V54.38 V (26.14%)31404.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.14 V (12.57%)181.9 V43.11 V (20.73%)24899.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.73 V (9.97%)187.3 V34.2 V (16.44%)19751.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.45 V (7.91%)191.6 V27.13 V (13.04%)15667.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.04 V (6.27%)195.0 V21.51 V (10.34%)12424.0 WDrop/Amp High
250 kcmil126.7 mm²255 A11.03 V (5.31%)197.0 V18.2 V (8.75%)10511.9 WDrop/Amp High
300 kcmil152.0 mm²285 A9.2 V (4.42%)198.8 V15.17 V (7.29%)8762.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.89 V (3.79%)200.1 V13.01 V (6.25%)7511.9 WDrop/Amp High
400 kcmil202.7 mm²335 A6.9 V (3.32%)201.1 V11.38 V (5.47%)6570.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.52 V (2.65%)202.5 V9.1 V (4.38%)5256.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.6 V (2.21%)203.4 V7.59 V (3.65%)4381.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.68 V (1.77%)204.3 V6.07 V (2.92%)3504.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.76 V (1.33%)205.2 V4.55 V (2.19%)2628.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 225 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.38V (0.67%) and delivers 206.6V at the load.

What size aluminum wire is required for 550 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.55V (2.19%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.