⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.67%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.26V (2.19%)
Voltage at Load End238.4 VLoss: 1.59 V (876.1 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A776.14 V (323.39%)0.0 V1280.27 V (533.45%)426877.5 WDrop/Amp High
12 AWG3.31 mm²20 A487.73 V (203.22%)0.0 V804.52 V (335.22%)268249.3 WDrop/Amp High
10 AWG5.26 mm²30 A306.92 V (127.88%)0.0 V506.27 V (210.94%)168803.3 WDrop/Amp High
8 AWG8.37 mm²50 A192.88 V (80.37%)47.1 V318.16 V (132.56%)106081.9 WDrop/Amp High
6 AWG13.3 mm²65 A121.38 V (50.58%)118.6 V200.22 V (83.43%)66759.8 WDrop/Amp High
4 AWG21.15 mm²85 A76.33 V (31.8%)163.7 V125.91 V (52.46%)41981.3 WDrop/Amp High
3 AWG26.67 mm²100 A60.53 V (25.22%)179.5 V99.85 V (41.6%)33292.3 WDrop/Amp High
2 AWG33.62 mm²115 A48.02 V (20.01%)192.0 V79.21 V (33.0%)26410.0 WDrop/Amp High
1 AWG42.41 mm²130 A38.07 V (15.86%)201.9 V62.79 V (26.16%)20936.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.18 V (12.58%)209.8 V49.78 V (20.74%)16599.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.94 V (9.98%)216.1 V39.49 V (16.46%)13167.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.99 V (7.91%)221.0 V31.33 V (13.05%)10444.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.06 V (6.27%)224.9 V24.84 V (10.35%)8282.7 WDrop/Amp High
250 kcmil126.7 mm²255 A12.74 V (5.31%)227.3 V21.02 V (8.76%)7007.9 WDrop/Amp High
300 kcmil152.0 mm²285 A10.62 V (4.43%)229.4 V17.52 V (7.3%)5841.5 WDrop/Amp High
350 kcmil177.3 mm²310 A9.11 V (3.79%)230.9 V15.02 V (6.26%)5007.9 WDrop/Amp High
400 kcmil202.7 mm²335 A7.96 V (3.32%)232.0 V13.14 V (5.47%)4380.4 WDrop/Amp High
500 kcmil253.4 mm²380 A6.37 V (2.65%)233.6 V10.51 V (4.38%)3504.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.31 V (2.21%)234.7 V8.76 V (3.65%)2920.7 WDrop/Amp High
750 kcmil380.0 mm²475 A4.25 V (1.77%)235.8 V7.01 V (2.92%)2336.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.19 V (1.33%)236.8 V5.26 V (2.19%)1752.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 225 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.59V (0.67%) and delivers 238.4V at the load.

What size aluminum wire is required for 550 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.26V (2.19%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.