550 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.48%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.84V (4.87%)
Voltage at Load End118.2 VLoss: 1.77 V (973.5 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A862.38 V (718.65%)0.0 V1422.52 V (1185.44%)474308.4 WDrop/Amp High
12 AWG3.31 mm²20 A541.92 V (451.6%)0.0 V893.91 V (744.93%)298054.8 WDrop/Amp High
10 AWG5.26 mm²30 A341.02 V (284.18%)0.0 V562.52 V (468.77%)187559.2 WDrop/Amp High
8 AWG8.37 mm²50 A214.31 V (178.59%)0.0 V353.51 V (294.59%)117868.7 WDrop/Amp High
6 AWG13.3 mm²65 A134.87 V (112.39%)0.0 V222.47 V (185.39%)74177.5 WDrop/Amp High
4 AWG21.15 mm²85 A84.81 V (70.68%)35.2 V139.9 V (116.58%)46645.9 WDrop/Amp High
3 AWG26.67 mm²100 A67.26 V (56.05%)52.7 V110.94 V (92.45%)36991.4 WDrop/Amp High
2 AWG33.62 mm²115 A53.35 V (44.46%)66.6 V88.01 V (73.34%)29344.5 WDrop/Amp High
1 AWG42.41 mm²130 A42.3 V (35.25%)77.7 V69.77 V (58.14%)23262.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A33.53 V (27.95%)86.5 V55.32 V (46.1%)18443.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.6 V (22.17%)93.4 V43.88 V (36.57%)14630.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.1 V (17.58%)98.9 V34.81 V (29.0%)11605.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.73 V (13.94%)103.3 V27.6 V (23.0%)9203.0 WDrop/Amp High
250 kcmil126.7 mm²255 A14.16 V (11.8%)105.8 V23.35 V (19.46%)7786.6 WDrop/Amp High
300 kcmil152.0 mm²285 A11.8 V (9.83%)108.2 V19.47 V (16.22%)6490.5 WDrop/Amp High
350 kcmil177.3 mm²310 A10.12 V (8.43%)109.9 V16.69 V (13.91%)5564.4 WDrop/Amp High
400 kcmil202.7 mm²335 A8.85 V (7.37%)111.2 V14.6 V (12.16%)4867.1 WDrop/Amp High
500 kcmil253.4 mm²380 A7.08 V (5.9%)112.9 V11.68 V (9.73%)3893.3 WDrop/Amp High
600 kcmil304.0 mm²420 A5.9 V (4.92%)114.1 V9.73 V (8.11%)3245.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.72 V (3.93%)115.3 V7.79 V (6.49%)2596.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.54 V (2.95%)116.5 V5.84 V (4.87%)1947.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 250 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.77V (1.48%) and delivers 118.2V at the load.

What size aluminum wire is required for 550 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.84V (4.87%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.