🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.06V (2.43%)
Voltage at Load End206.5 VLoss: 1.53 V (1460.2 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A746.84 V (359.06%)0.0 V1231.94 V (592.28%)711462.5 WDrop/Amp High
12 AWG3.31 mm²20 A469.31 V (225.63%)0.0 V774.15 V (372.19%)447082.2 WDrop/Amp High
10 AWG5.26 mm²30 A295.33 V (141.99%)0.0 V487.16 V (234.21%)281338.8 WDrop/Amp High
8 AWG8.37 mm²50 A185.6 V (89.23%)22.4 V306.15 V (147.19%)176803.1 WDrop/Amp High
6 AWG13.3 mm²65 A116.8 V (56.15%)91.2 V192.66 V (92.63%)111266.3 WDrop/Amp High
4 AWG21.15 mm²85 A73.45 V (35.31%)134.6 V121.16 V (58.25%)69968.9 WDrop/Amp High
3 AWG26.67 mm²100 A58.25 V (28.0%)149.8 V96.08 V (46.19%)55487.1 WDrop/Amp High
2 AWG33.62 mm²115 A46.21 V (22.21%)161.8 V76.22 V (36.64%)44016.7 WDrop/Amp High
1 AWG42.41 mm²130 A36.63 V (17.61%)171.4 V60.42 V (29.05%)34893.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.04 V (13.96%)179.0 V47.9 V (23.03%)27665.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.04 V (11.08%)185.0 V38.0 V (18.27%)21946.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.27 V (8.79%)189.7 V30.14 V (14.49%)17407.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.49 V (6.97%)193.5 V23.9 V (11.49%)13804.5 WDrop/Amp High
250 kcmil126.7 mm²255 A12.26 V (5.89%)195.7 V20.22 V (9.72%)11679.9 WDrop/Amp High
300 kcmil152.0 mm²285 A10.22 V (4.91%)197.8 V16.86 V (8.1%)9735.8 WDrop/Amp High
350 kcmil177.3 mm²310 A8.76 V (4.21%)199.2 V14.45 V (6.95%)8346.5 WDrop/Amp High
400 kcmil202.7 mm²335 A7.66 V (3.68%)200.3 V12.64 V (6.08%)7300.7 WDrop/Amp High
500 kcmil253.4 mm²380 A6.13 V (2.95%)201.9 V10.11 V (4.86%)5839.9 WDrop/Amp High
600 kcmil304.0 mm²420 A5.11 V (2.46%)202.9 V8.43 V (4.05%)4867.9 WDrop/Amp High
750 kcmil380.0 mm²475 A4.09 V (1.97%)203.9 V6.74 V (3.24%)3894.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.07 V (1.47%)204.9 V5.06 V (2.43%)2920.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 250 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.53V (0.73%) and delivers 206.5V at the load.

What size aluminum wire is required for 550 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.06V (2.43%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.