🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 300 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.07V (1.26%)
Voltage at Load End478.2 VLoss: 1.84 V (1752.3 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 300 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A896.21 V (186.71%)0.0 V1478.33 V (307.99%)853755.1 WDrop/Amp High
12 AWG3.31 mm²20 A563.18 V (117.33%)0.0 V928.98 V (193.54%)536498.6 WDrop/Amp High
10 AWG5.26 mm²30 A354.39 V (73.83%)125.6 V584.59 V (121.79%)337606.6 WDrop/Amp High
8 AWG8.37 mm²50 A222.71 V (46.4%)257.3 V367.37 V (76.54%)212163.7 WDrop/Amp High
6 AWG13.3 mm²65 A140.16 V (29.2%)339.8 V231.2 V (48.17%)133519.6 WDrop/Amp High
4 AWG21.15 mm²85 A88.14 V (18.36%)391.9 V145.39 V (30.29%)83962.7 WDrop/Amp High
3 AWG26.67 mm²100 A69.9 V (14.56%)410.1 V115.3 V (24.02%)66584.6 WDrop/Amp High
2 AWG33.62 mm²115 A55.45 V (11.55%)424.6 V91.46 V (19.05%)52820.1 WDrop/Amp High
1 AWG42.41 mm²130 A43.95 V (9.16%)436.0 V72.5 V (15.11%)41872.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A34.85 V (7.26%)445.2 V57.49 V (11.98%)33198.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.65 V (5.76%)452.4 V45.6 V (9.5%)26335.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A21.93 V (4.57%)458.1 V36.17 V (7.54%)20889.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.39 V (3.62%)462.6 V28.68 V (5.98%)16565.4 WDrop/Amp High
250 kcmil126.7 mm²255 A14.71 V (3.07%)465.3 V24.27 V (5.06%)14015.9 WDrop/Amp High
300 kcmil152.0 mm²285 A12.26 V (2.55%)467.7 V20.23 V (4.21%)11683.0 WDrop/Amp High
350 kcmil177.3 mm²310 A10.51 V (2.19%)469.5 V17.34 V (3.61%)10015.9 WDrop/Amp High
400 kcmil202.7 mm²335 A9.2 V (1.92%)470.8 V15.17 V (3.16%)8760.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.36 V (1.53%)472.6 V12.13 V (2.53%)7007.9 WDrop/Amp High
600 kcmil304.0 mm²420 A6.13 V (1.28%)473.9 V10.11 V (2.11%)5841.5 WDrop/Amp High
750 kcmil380.0 mm²475 A4.91 V (1.02%)475.1 V8.09 V (1.69%)4673.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.68 V (0.77%)476.3 V6.07 V (1.26%)3504.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 300 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 300 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.84V (0.39%) and delivers 478.2V at the load.

What size aluminum wire is required for 550 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.07V (1.26%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.