550 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.51%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.09V (1.69%)
Voltage at Load End477.5 VLoss: 2.46 V (2336.4 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1194.95 V (248.95%)0.0 V1971.1 V (410.65%)1138340.1 WDrop/Amp High
12 AWG3.31 mm²20 A750.9 V (156.44%)0.0 V1238.64 V (258.05%)715331.5 WDrop/Amp High
10 AWG5.26 mm²30 A472.53 V (98.44%)7.5 V779.45 V (162.39%)450142.1 WDrop/Amp High
8 AWG8.37 mm²50 A296.95 V (61.87%)183.0 V489.83 V (102.05%)282885.0 WDrop/Amp High
6 AWG13.3 mm²65 A186.88 V (38.93%)293.1 V308.26 V (64.22%)178026.1 WDrop/Amp High
4 AWG21.15 mm²85 A117.52 V (24.48%)362.5 V193.85 V (40.39%)111950.2 WDrop/Amp High
3 AWG26.67 mm²100 A93.19 V (19.42%)386.8 V153.73 V (32.03%)88779.4 WDrop/Amp High
2 AWG33.62 mm²115 A73.93 V (15.4%)406.1 V121.95 V (25.41%)70426.8 WDrop/Amp High
1 AWG42.41 mm²130 A58.61 V (12.21%)421.4 V96.67 V (20.14%)55829.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A46.47 V (9.68%)433.5 V76.65 V (15.97%)44265.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A36.86 V (7.68%)443.1 V60.8 V (12.67%)35114.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.24 V (6.09%)450.8 V48.23 V (10.05%)27852.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.19 V (4.83%)456.8 V38.25 V (7.97%)22087.2 WDrop/Amp High
250 kcmil126.7 mm²255 A19.62 V (4.09%)460.4 V32.36 V (6.74%)18687.8 WDrop/Amp High
300 kcmil152.0 mm²285 A16.35 V (3.41%)463.6 V26.97 V (5.62%)15577.3 WDrop/Amp High
350 kcmil177.3 mm²310 A14.02 V (2.92%)466.0 V23.12 V (4.82%)13354.5 WDrop/Amp High
400 kcmil202.7 mm²335 A12.26 V (2.55%)467.7 V20.23 V (4.21%)11681.0 WDrop/Amp High
500 kcmil253.4 mm²380 A9.81 V (2.04%)470.2 V16.18 V (3.37%)9343.9 WDrop/Amp High
600 kcmil304.0 mm²420 A8.18 V (1.7%)471.8 V13.49 V (2.81%)7788.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.54 V (1.36%)473.5 V10.79 V (2.25%)6230.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.91 V (1.02%)475.1 V8.09 V (1.69%)4672.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 400 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.46V (0.51%) and delivers 477.5V at the load.

What size aluminum wire is required for 550 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.09V (1.69%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.