⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.77%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.01V (5.84%)
Voltage at Load End235.8 VLoss: 4.25 V (2336.4 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2069.71 V (862.38%)0.0 V3414.05 V (1422.52%)1138340.1 WDrop/Amp High
12 AWG3.31 mm²20 A1300.6 V (541.92%)0.0 V2145.39 V (893.91%)715331.5 WDrop/Amp High
10 AWG5.26 mm²30 A818.44 V (341.02%)0.0 V1350.04 V (562.52%)450142.1 WDrop/Amp High
8 AWG8.37 mm²50 A514.34 V (214.31%)0.0 V848.41 V (353.51%)282885.0 WDrop/Amp High
6 AWG13.3 mm²65 A323.68 V (134.87%)0.0 V533.93 V (222.47%)178026.1 WDrop/Amp High
4 AWG21.15 mm²85 A203.55 V (84.81%)36.5 V335.76 V (139.9%)111950.2 WDrop/Amp High
3 AWG26.67 mm²100 A161.42 V (67.26%)78.6 V266.26 V (110.94%)88779.4 WDrop/Amp High
2 AWG33.62 mm²115 A128.05 V (53.35%)112.0 V211.22 V (88.01%)70426.8 WDrop/Amp High
1 AWG42.41 mm²130 A101.51 V (42.3%)138.5 V167.44 V (69.77%)55829.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A80.48 V (33.53%)159.5 V132.76 V (55.32%)44265.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A63.84 V (26.6%)176.2 V105.31 V (43.88%)35114.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A50.64 V (21.1%)189.4 V83.53 V (34.81%)27852.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A40.16 V (16.73%)199.8 V66.24 V (27.6%)22087.2 WDrop/Amp High
250 kcmil126.7 mm²255 A33.98 V (14.16%)206.0 V56.05 V (23.35%)18687.8 WDrop/Amp High
300 kcmil152.0 mm²285 A28.32 V (11.8%)211.7 V46.72 V (19.47%)15577.3 WDrop/Amp High
350 kcmil177.3 mm²310 A24.28 V (10.12%)215.7 V40.05 V (16.69%)13354.5 WDrop/Amp High
400 kcmil202.7 mm²335 A21.24 V (8.85%)218.8 V35.03 V (14.6%)11681.0 WDrop/Amp High
500 kcmil253.4 mm²380 A16.99 V (7.08%)223.0 V28.02 V (11.68%)9343.9 WDrop/Amp High
600 kcmil304.0 mm²420 A14.16 V (5.9%)225.8 V23.36 V (9.73%)7788.6 WDrop/Amp High
750 kcmil380.0 mm²475 A11.33 V (4.72%)228.7 V18.69 V (7.79%)6230.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.5 V (3.54%)231.5 V14.01 V (5.84%)4672.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.25V (1.77%) and delivers 235.8V at the load.

What size aluminum wire is required for 550 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.01V (5.84%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.