⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.36%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 18.69V (15.57%)
Voltage at Load End117.2 VLoss: 2.83 V (1557.6 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2759.61 V (2299.68%)0.0 V4552.07 V (3793.39%)1517786.8 WDrop/Amp High
12 AWG3.31 mm²20 A1734.14 V (1445.11%)0.0 V2860.52 V (2383.76%)953775.4 WDrop/Amp High
10 AWG5.26 mm²30 A1091.25 V (909.38%)0.0 V1800.06 V (1500.05%)600189.4 WDrop/Amp High
8 AWG8.37 mm²50 A685.78 V (571.48%)0.0 V1131.22 V (942.68%)377180.0 WDrop/Amp High
6 AWG13.3 mm²65 A431.58 V (359.65%)0.0 V711.9 V (593.25%)237368.2 WDrop/Amp High
4 AWG21.15 mm²85 A271.39 V (226.16%)0.0 V447.67 V (373.06%)149267.0 WDrop/Amp High
3 AWG26.67 mm²100 A215.22 V (179.35%)0.0 V355.02 V (295.85%)118372.6 WDrop/Amp High
2 AWG33.62 mm²115 A170.73 V (142.28%)0.0 V281.63 V (234.69%)93902.3 WDrop/Amp High
1 AWG42.41 mm²130 A135.35 V (112.79%)0.0 V223.26 V (186.05%)74439.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A107.31 V (89.42%)12.7 V177.01 V (147.51%)59020.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A85.13 V (70.94%)34.9 V140.42 V (117.01%)46818.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A67.52 V (56.27%)52.5 V111.38 V (92.82%)37136.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A53.54 V (44.62%)66.5 V88.32 V (73.6%)29449.6 WDrop/Amp High
250 kcmil126.7 mm²255 A45.3 V (37.75%)74.7 V74.73 V (62.28%)24917.1 WDrop/Amp High
300 kcmil152.0 mm²285 A37.76 V (31.47%)82.2 V62.29 V (51.91%)20769.7 WDrop/Amp High
350 kcmil177.3 mm²310 A32.37 V (26.98%)87.6 V53.4 V (44.5%)17806.0 WDrop/Amp High
400 kcmil202.7 mm²335 A28.32 V (23.6%)91.7 V46.71 V (38.93%)15574.7 WDrop/Amp High
500 kcmil253.4 mm²380 A22.65 V (18.88%)97.3 V37.37 V (31.14%)12458.5 WDrop/Amp High
600 kcmil304.0 mm²420 A18.88 V (15.73%)101.1 V31.15 V (25.95%)10384.9 WDrop/Amp High
750 kcmil380.0 mm²475 A15.11 V (12.59%)104.9 V24.92 V (20.76%)8307.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.33 V (9.44%)108.7 V18.69 V (15.57%)6230.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 800 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.83V (2.36%) and delivers 117.2V at the load.

What size aluminum wire is required for 550 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 18.69V (15.57%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.