⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.92V (3.72%)
Voltage at Load End237.3 VLoss: 2.71 V (1622.0 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1317.09 V (548.79%)0.0 V2172.58 V (905.24%)790252.6 WDrop/Amp High
12 AWG3.31 mm²20 A827.66 V (344.86%)0.0 V1365.25 V (568.85%)496593.8 WDrop/Amp High
10 AWG5.26 mm²30 A520.83 V (217.01%)0.0 V859.12 V (357.97%)312495.3 WDrop/Amp High
8 AWG8.37 mm²50 A327.3 V (136.38%)0.0 V539.9 V (224.96%)196383.0 WDrop/Amp High
6 AWG13.3 mm²65 A205.98 V (85.83%)34.0 V339.77 V (141.57%)123588.4 WDrop/Amp High
4 AWG21.15 mm²85 A129.53 V (53.97%)110.5 V213.66 V (89.03%)77717.5 WDrop/Amp High
3 AWG26.67 mm²100 A102.72 V (42.8%)137.3 V169.44 V (70.6%)61632.0 WDrop/Amp High
2 AWG33.62 mm²115 A81.49 V (33.95%)158.5 V134.41 V (56.01%)48891.3 WDrop/Amp High
1 AWG42.41 mm²130 A64.6 V (26.92%)175.4 V106.55 V (44.4%)38758.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.22 V (21.34%)188.8 V84.48 V (35.2%)30729.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A40.63 V (16.93%)199.4 V67.02 V (27.92%)24376.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.23 V (13.43%)207.8 V53.16 V (22.15%)19335.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.56 V (10.65%)214.4 V42.15 V (17.56%)15333.3 WDrop/Amp High
250 kcmil126.7 mm²255 A21.62 V (9.01%)218.4 V35.67 V (14.86%)12973.4 WDrop/Amp High
300 kcmil152.0 mm²285 A18.02 V (7.51%)222.0 V29.73 V (12.39%)10814.0 WDrop/Amp High
350 kcmil177.3 mm²310 A15.45 V (6.44%)224.5 V25.49 V (10.62%)9270.9 WDrop/Amp High
400 kcmil202.7 mm²335 A13.52 V (5.63%)226.5 V22.29 V (9.29%)8109.2 WDrop/Amp High
500 kcmil253.4 mm²380 A10.81 V (4.5%)229.2 V17.83 V (7.43%)6486.7 WDrop/Amp High
600 kcmil304.0 mm²420 A9.01 V (3.75%)231.0 V14.87 V (6.19%)5407.0 WDrop/Amp High
750 kcmil380.0 mm²475 A7.21 V (3.0%)232.8 V11.89 V (4.96%)4325.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.41 V (2.25%)234.6 V8.92 V (3.72%)3244.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 350 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.71V (1.12%) and delivers 237.3V at the load.

What size aluminum wire is required for 600 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.92V (3.72%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.