600 Amp Wire Size at 400 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.19V (4.25%)
Voltage at Load End236.9 VLoss: 3.09 V (1853.7 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1505.24 V (627.18%)0.0 V2482.95 V (1034.56%)903145.8 WDrop/Amp High
12 AWG3.31 mm²20 A945.89 V (394.12%)0.0 V1560.28 V (650.12%)567535.8 WDrop/Amp High
10 AWG5.26 mm²30 A595.23 V (248.01%)0.0 V981.85 V (409.1%)357137.5 WDrop/Amp High
8 AWG8.37 mm²50 A374.06 V (155.86%)0.0 V617.03 V (257.1%)224437.7 WDrop/Amp High
6 AWG13.3 mm²65 A235.41 V (98.09%)4.6 V388.31 V (161.8%)141243.9 WDrop/Amp High
4 AWG21.15 mm²85 A148.03 V (61.68%)92.0 V244.19 V (101.74%)88820.0 WDrop/Amp High
3 AWG26.67 mm²100 A117.39 V (48.91%)122.6 V193.65 V (80.69%)70436.6 WDrop/Amp High
2 AWG33.62 mm²115 A93.13 V (38.8%)146.9 V153.61 V (64.01%)55875.8 WDrop/Amp High
1 AWG42.41 mm²130 A73.82 V (30.76%)166.2 V121.78 V (50.74%)44294.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A58.53 V (24.39%)181.5 V96.55 V (40.23%)35119.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A46.43 V (19.35%)193.6 V76.59 V (31.91%)27859.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A36.83 V (15.35%)203.2 V60.75 V (25.31%)22097.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A29.21 V (12.17%)210.8 V48.18 V (20.07%)17523.7 WDrop/Amp High
250 kcmil126.7 mm²255 A24.71 V (10.3%)215.3 V40.76 V (16.98%)14826.7 WDrop/Amp High
300 kcmil152.0 mm²285 A20.6 V (8.58%)219.4 V33.98 V (14.16%)12358.8 WDrop/Amp High
350 kcmil177.3 mm²310 A17.66 V (7.36%)222.3 V29.13 V (12.14%)10595.3 WDrop/Amp High
400 kcmil202.7 mm²335 A15.45 V (6.44%)224.6 V25.48 V (10.62%)9267.6 WDrop/Amp High
500 kcmil253.4 mm²380 A12.36 V (5.15%)227.6 V20.38 V (8.49%)7413.4 WDrop/Amp High
600 kcmil304.0 mm²420 A10.3 V (4.29%)229.7 V16.99 V (7.08%)6179.4 WDrop/Amp High
750 kcmil380.0 mm²475 A8.24 V (3.43%)231.8 V13.59 V (5.66%)4943.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.18 V (2.57%)233.8 V10.19 V (4.25%)3707.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 400 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.09V (1.28%) and delivers 236.9V at the load.

What size aluminum wire is required for 600 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.19V (4.25%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.