⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.03V (5.3%)
Voltage at Load End204.7 VLoss: 3.35 V (3475.7 W)
Power & Breaker (125%)216.16 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1629.47 V (783.4%)0.0 V2687.87 V (1292.25%)1693398.5 WDrop/Amp High
12 AWG3.31 mm²20 A1023.96 V (492.29%)0.0 V1689.05 V (812.05%)1064129.5 WDrop/Amp High
10 AWG5.26 mm²30 A644.35 V (309.79%)0.0 V1062.88 V (511.0%)669632.9 WDrop/Amp High
8 AWG8.37 mm²50 A404.93 V (194.68%)0.0 V667.95 V (321.13%)420820.6 WDrop/Amp High
6 AWG13.3 mm²65 A254.83 V (122.52%)0.0 V420.36 V (202.1%)264832.2 WDrop/Amp High
4 AWG21.15 mm²85 A160.25 V (77.04%)47.7 V264.34 V (127.09%)166537.5 WDrop/Amp High
3 AWG26.67 mm²100 A127.08 V (61.1%)80.9 V209.63 V (100.78%)132068.6 WDrop/Amp High
2 AWG33.62 mm²115 A100.81 V (48.47%)107.2 V166.29 V (79.95%)104767.1 WDrop/Amp High
1 AWG42.41 mm²130 A79.92 V (38.42%)128.1 V131.83 V (63.38%)83052.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A63.36 V (30.46%)144.6 V104.52 V (50.25%)65849.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A50.26 V (24.17%)157.7 V82.91 V (39.86%)52235.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A39.87 V (19.17%)168.1 V65.77 V (31.62%)41433.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A31.62 V (15.2%)176.4 V52.15 V (25.07%)32857.0 WDrop/Amp High
250 kcmil126.7 mm²255 A26.75 V (12.86%)181.2 V44.13 V (21.21%)27800.1 WDrop/Amp High
300 kcmil152.0 mm²285 A22.3 V (10.72%)185.7 V36.78 V (17.68%)23172.8 WDrop/Amp High
350 kcmil177.3 mm²310 A19.12 V (9.19%)188.9 V31.53 V (15.16%)19866.2 WDrop/Amp High
400 kcmil202.7 mm²335 A16.72 V (8.04%)191.3 V27.58 V (13.26%)17376.8 WDrop/Amp High
500 kcmil253.4 mm²380 A13.38 V (6.43%)194.6 V22.06 V (10.61%)13900.0 WDrop/Amp High
600 kcmil304.0 mm²420 A11.15 V (5.36%)196.9 V18.39 V (8.84%)11586.4 WDrop/Amp High
750 kcmil380.0 mm²475 A8.92 V (4.29%)199.1 V14.71 V (7.07%)9269.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.69 V (3.22%)201.3 V11.03 V (5.3%)6951.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 500 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.35V (1.61%) and delivers 204.7V at the load.

What size aluminum wire is required for 600 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.03V (5.3%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.