🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 200 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (4.6%)
Voltage at Load End118.3 VLoss: 1.68 V (1087.8 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 200 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A815.34 V (679.45%)0.0 V1344.93 V (1120.78%)529971.0 WDrop/Amp High
12 AWG3.31 mm²20 A512.36 V (426.97%)0.0 V845.15 V (704.29%)333033.1 WDrop/Amp High
10 AWG5.26 mm²30 A322.42 V (268.68%)0.0 V531.84 V (443.2%)209570.3 WDrop/Amp High
8 AWG8.37 mm²50 A202.62 V (168.85%)0.0 V334.22 V (278.52%)131701.3 WDrop/Amp High
6 AWG13.3 mm²65 A127.51 V (106.26%)0.0 V210.33 V (175.28%)82882.7 WDrop/Amp High
4 AWG21.15 mm²85 A80.18 V (66.82%)39.8 V132.27 V (110.22%)52120.1 WDrop/Amp High
3 AWG26.67 mm²100 A63.59 V (52.99%)56.4 V104.89 V (87.41%)41332.6 WDrop/Amp High
2 AWG33.62 mm²115 A50.44 V (42.04%)69.6 V83.21 V (69.34%)32788.2 WDrop/Amp High
1 AWG42.41 mm²130 A39.99 V (33.32%)80.0 V65.96 V (54.97%)25992.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.71 V (26.42%)88.3 V52.3 V (43.58%)20608.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.15 V (20.96%)94.8 V41.49 V (34.57%)16347.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.95 V (16.62%)100.1 V32.91 V (27.42%)12967.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.82 V (13.18%)104.2 V26.1 V (21.75%)10283.0 WDrop/Amp High
250 kcmil126.7 mm²255 A13.39 V (11.15%)106.6 V22.08 V (18.4%)8700.4 WDrop/Amp High
300 kcmil152.0 mm²285 A11.16 V (9.3%)108.8 V18.4 V (15.34%)7252.2 WDrop/Amp High
350 kcmil177.3 mm²310 A9.57 V (7.97%)110.4 V15.78 V (13.15%)6217.4 WDrop/Amp High
400 kcmil202.7 mm²335 A8.37 V (6.97%)111.6 V13.8 V (11.5%)5438.3 WDrop/Amp High
500 kcmil253.4 mm²380 A6.69 V (5.58%)113.3 V11.04 V (9.2%)4350.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.58 V (4.65%)114.4 V9.2 V (7.67%)3626.1 WDrop/Amp High
750 kcmil380.0 mm²475 A4.46 V (3.72%)115.5 V7.36 V (6.13%)2900.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.35 V (2.79%)116.7 V5.52 V (4.6%)2175.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 200 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 200 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.68V (1.4%) and delivers 118.3V at the load.

What size aluminum wire is required for 650 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (4.6%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.