🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.38V (2.59%)
Voltage at Load End206.4 VLoss: 1.63 V (1835.6 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A794.37 V (381.91%)0.0 V1310.34 V (629.97%)894326.1 WDrop/Amp High
12 AWG3.31 mm²20 A499.18 V (239.99%)0.0 V823.41 V (395.87%)561993.4 WDrop/Amp High
10 AWG5.26 mm²30 A314.12 V (151.02%)0.0 V518.16 V (249.11%)353649.8 WDrop/Amp High
8 AWG8.37 mm²50 A197.41 V (94.91%)10.6 V325.63 V (156.55%)222245.9 WDrop/Amp High
6 AWG13.3 mm²65 A124.23 V (59.73%)83.8 V204.92 V (98.52%)139864.5 WDrop/Amp High
4 AWG21.15 mm²85 A78.12 V (37.56%)129.9 V128.87 V (61.95%)87952.6 WDrop/Amp High
3 AWG26.67 mm²100 A61.95 V (29.79%)146.0 V102.19 V (49.13%)69748.7 WDrop/Amp High
2 AWG33.62 mm²115 A49.15 V (23.63%)158.9 V81.07 V (38.97%)55330.1 WDrop/Amp High
1 AWG42.41 mm²130 A38.96 V (18.73%)169.0 V64.27 V (30.9%)43862.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.89 V (14.85%)177.1 V50.95 V (24.5%)34776.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.5 V (11.78%)183.5 V40.42 V (19.43%)27587.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.44 V (9.34%)188.6 V32.06 V (15.41%)21882.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.41 V (7.41%)192.6 V25.42 V (12.22%)17352.6 WDrop/Amp High
250 kcmil126.7 mm²255 A13.04 V (6.27%)195.0 V21.51 V (10.34%)14681.9 WDrop/Amp High
300 kcmil152.0 mm²285 A10.87 V (5.23%)197.1 V17.93 V (8.62%)12238.1 WDrop/Amp High
350 kcmil177.3 mm²310 A9.32 V (4.48%)198.7 V15.37 V (7.39%)10491.8 WDrop/Amp High
400 kcmil202.7 mm²335 A8.15 V (3.92%)199.8 V13.45 V (6.46%)9177.1 WDrop/Amp High
500 kcmil253.4 mm²380 A6.52 V (3.13%)201.5 V10.76 V (5.17%)7341.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.44 V (2.61%)202.6 V8.97 V (4.31%)6119.1 WDrop/Amp High
750 kcmil380.0 mm²475 A4.35 V (2.09%)203.7 V7.17 V (3.45%)4895.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.26 V (1.57%)204.7 V5.38 V (2.59%)3671.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 225 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.63V (0.79%) and delivers 206.4V at the load.

What size aluminum wire is required for 650 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.38V (2.59%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.