🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 350 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.66V (8.05%)
Voltage at Load End117.1 VLoss: 2.93 V (1903.6 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 350 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1426.85 V (1189.04%)0.0 V2353.63 V (1961.36%)927449.2 WDrop/Amp High
12 AWG3.31 mm²20 A896.63 V (747.19%)0.0 V1479.02 V (1232.51%)582808.0 WDrop/Amp High
10 AWG5.26 mm²30 A564.23 V (470.19%)0.0 V930.71 V (775.59%)366748.0 WDrop/Amp High
8 AWG8.37 mm²50 A354.58 V (295.48%)0.0 V584.89 V (487.41%)230477.2 WDrop/Amp High
6 AWG13.3 mm²65 A223.15 V (185.95%)0.0 V368.09 V (306.74%)145044.7 WDrop/Amp High
4 AWG21.15 mm²85 A140.32 V (116.94%)0.0 V231.47 V (192.89%)91210.1 WDrop/Amp High
3 AWG26.67 mm²100 A111.28 V (92.73%)8.7 V183.56 V (152.97%)72332.0 WDrop/Amp High
2 AWG33.62 mm²115 A88.28 V (73.56%)31.7 V145.61 V (121.35%)57379.4 WDrop/Amp High
1 AWG42.41 mm²130 A69.98 V (58.32%)50.0 V115.43 V (96.19%)45486.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A55.48 V (46.24%)64.5 V91.52 V (76.27%)36064.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A44.01 V (36.68%)76.0 V72.6 V (60.5%)28608.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.91 V (29.09%)85.1 V57.59 V (47.99%)22692.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.69 V (23.07%)92.3 V45.67 V (38.06%)17995.3 WDrop/Amp High
250 kcmil126.7 mm²255 A23.42 V (19.52%)96.6 V38.64 V (32.2%)15225.7 WDrop/Amp High
300 kcmil152.0 mm²285 A19.53 V (16.27%)100.5 V32.21 V (26.84%)12691.4 WDrop/Amp High
350 kcmil177.3 mm²310 A16.74 V (13.95%)103.3 V27.61 V (23.01%)10880.4 WDrop/Amp High
400 kcmil202.7 mm²335 A14.64 V (12.2%)105.4 V24.15 V (20.13%)9517.0 WDrop/Amp High
500 kcmil253.4 mm²380 A11.71 V (9.76%)108.3 V19.32 V (16.1%)7612.8 WDrop/Amp High
600 kcmil304.0 mm²420 A9.76 V (8.14%)110.2 V16.1 V (13.42%)6345.7 WDrop/Amp High
750 kcmil380.0 mm²475 A7.81 V (6.51%)112.2 V12.88 V (10.74%)5076.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.86 V (4.88%)114.1 V9.66 V (8.05%)3807.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 350 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 350 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.93V (2.44%) and delivers 117.1V at the load.

What size aluminum wire is required for 650 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.66V (8.05%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.