🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.8V (5.75%)
Voltage at Load End235.8 VLoss: 4.18 V (2719.4 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2038.35 V (849.31%)0.0 V3362.32 V (1400.97%)1324927.5 WDrop/Amp High
12 AWG3.31 mm²20 A1280.9 V (533.71%)0.0 V2112.88 V (880.37%)832582.8 WDrop/Amp High
10 AWG5.26 mm²30 A806.04 V (335.85%)0.0 V1329.59 V (554.0%)523925.7 WDrop/Amp High
8 AWG8.37 mm²50 A506.54 V (211.06%)0.0 V835.56 V (348.15%)329253.2 WDrop/Amp High
6 AWG13.3 mm²65 A318.78 V (132.82%)0.0 V525.84 V (219.1%)207206.7 WDrop/Amp High
4 AWG21.15 mm²85 A200.46 V (83.53%)39.5 V330.67 V (137.78%)130300.2 WDrop/Amp High
3 AWG26.67 mm²100 A158.97 V (66.24%)81.0 V262.23 V (109.26%)103331.4 WDrop/Amp High
2 AWG33.62 mm²115 A126.11 V (52.55%)113.9 V208.02 V (86.68%)81970.5 WDrop/Amp High
1 AWG42.41 mm²130 A99.97 V (41.65%)140.0 V164.91 V (68.71%)64981.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A79.26 V (33.03%)160.7 V130.75 V (54.48%)51520.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A62.88 V (26.2%)177.1 V103.72 V (43.22%)40869.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A49.87 V (20.78%)190.1 V82.27 V (34.28%)32417.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A39.55 V (16.48%)200.4 V65.24 V (27.18%)25707.5 WDrop/Amp High
250 kcmil126.7 mm²255 A33.46 V (13.94%)206.5 V55.2 V (23.0%)21751.0 WDrop/Amp High
300 kcmil152.0 mm²285 A27.89 V (11.62%)212.1 V46.01 V (19.17%)18130.6 WDrop/Amp High
350 kcmil177.3 mm²310 A23.91 V (9.96%)216.1 V39.45 V (16.44%)15543.4 WDrop/Amp High
400 kcmil202.7 mm²335 A20.92 V (8.72%)219.1 V34.5 V (14.38%)13595.7 WDrop/Amp High
500 kcmil253.4 mm²380 A16.73 V (6.97%)223.3 V27.6 V (11.5%)10875.5 WDrop/Amp High
600 kcmil304.0 mm²420 A13.95 V (5.81%)226.1 V23.01 V (9.59%)9065.3 WDrop/Amp High
750 kcmil380.0 mm²475 A11.16 V (4.65%)228.8 V18.4 V (7.67%)7252.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.37 V (3.49%)231.6 V13.8 V (5.75%)5438.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 500 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.18V (1.75%) and delivers 235.8V at the load.

What size aluminum wire is required for 650 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.8V (5.75%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.