⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 1000 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)51× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 29.73V (247.73%)
Voltage at Load End11.7 VLoss: 0.35 V (247.4 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 1000 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4390.29 V (36585.77%)0.0 V7241.93 V (60349.42%)3073204.6 WDrop/Amp High
12 AWG3.31 mm²20 A2758.85 V (22990.45%)0.0 V4550.82 V (37923.5%)1931198.1 WDrop/Amp High
10 AWG5.26 mm²30 A1736.09 V (14467.38%)0.0 V2863.73 V (23864.41%)1215259.6 WDrop/Amp High
8 AWG8.37 mm²50 A1091.02 V (9091.8%)0.0 V1799.67 V (14997.23%)763711.5 WDrop/Amp High
6 AWG13.3 mm²65 A686.6 V (5721.68%)0.0 V1132.57 V (9438.11%)480621.5 WDrop/Amp High
4 AWG21.15 mm²85 A431.76 V (3598.03%)0.0 V712.21 V (5935.07%)302234.8 WDrop/Amp High
3 AWG26.67 mm²100 A342.4 V (2853.33%)0.0 V564.8 V (4706.67%)239680.0 WDrop/Amp High
2 AWG33.62 mm²115 A271.62 V (2263.49%)0.0 V448.04 V (3733.69%)190132.8 WDrop/Amp High
1 AWG42.41 mm²130 A215.32 V (1794.35%)0.0 V355.18 V (2959.84%)150725.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A170.72 V (1422.67%)0.0 V281.61 V (2346.73%)119503.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A135.43 V (1128.55%)0.0 V223.39 V (1861.59%)94798.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A107.42 V (895.17%)0.0 V177.19 V (1476.61%)75194.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A85.18 V (709.87%)0.0 V140.52 V (1170.96%)59629.3 WDrop/Amp High
250 kcmil126.7 mm²255 A72.07 V (600.62%)0.0 V118.89 V (990.74%)50452.0 WDrop/Amp High
300 kcmil152.0 mm²285 A60.08 V (500.65%)0.0 V99.1 V (825.83%)42054.4 WDrop/Amp High
350 kcmil177.3 mm²310 A51.5 V (429.21%)0.0 V84.96 V (707.99%)36053.4 WDrop/Amp High
400 kcmil202.7 mm²335 A45.05 V (375.42%)0.0 V74.31 V (619.27%)31535.6 WDrop/Amp High
500 kcmil253.4 mm²380 A36.04 V (300.31%)0.0 V59.44 V (495.37%)25226.0 WDrop/Amp High
600 kcmil304.0 mm²420 A30.04 V (250.32%)0.0 V49.55 V (412.92%)21027.2 WDrop/Amp High
750 kcmil380.0 mm²475 A24.03 V (200.26%)0.0 V39.64 V (330.33%)16821.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A18.02 V (150.18%)0.0 V29.73 V (247.73%)12615.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 1000 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 1000 feet one-way at 12V (DC), you need 51× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.94%) and delivers 11.7V at the load.

What size aluminum wire is required for 700 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 29.73V (247.73%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.