⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.43V (6.19%)
Voltage at Load End117.8 VLoss: 2.25 V (1577.0 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1097.57 V (914.64%)0.0 V1810.48 V (1508.74%)768301.2 WDrop/Amp High
12 AWG3.31 mm²20 A689.71 V (574.76%)0.0 V1137.71 V (948.09%)482799.5 WDrop/Amp High
10 AWG5.26 mm²30 A434.02 V (361.68%)0.0 V715.93 V (596.61%)303814.9 WDrop/Amp High
8 AWG8.37 mm²50 A272.75 V (227.3%)0.0 V449.92 V (374.93%)190927.9 WDrop/Amp High
6 AWG13.3 mm²65 A171.65 V (143.04%)0.0 V283.14 V (235.95%)120155.4 WDrop/Amp High
4 AWG21.15 mm²85 A107.94 V (89.95%)12.1 V178.05 V (148.38%)75558.7 WDrop/Amp High
3 AWG26.67 mm²100 A85.6 V (71.33%)34.4 V141.2 V (117.67%)59920.0 WDrop/Amp High
2 AWG33.62 mm²115 A67.9 V (56.59%)52.1 V112.01 V (93.34%)47533.2 WDrop/Amp High
1 AWG42.41 mm²130 A53.83 V (44.86%)66.2 V88.8 V (74.0%)37681.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A42.68 V (35.57%)77.3 V70.4 V (58.67%)29876.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A33.86 V (28.21%)86.1 V55.85 V (46.54%)23699.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A26.86 V (22.38%)93.1 V44.3 V (36.92%)18798.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A21.3 V (17.75%)98.7 V35.13 V (29.27%)14907.3 WDrop/Amp High
250 kcmil126.7 mm²255 A18.02 V (15.02%)102.0 V29.72 V (24.77%)12613.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.02 V (12.52%)105.0 V24.78 V (20.65%)10513.6 WDrop/Amp High
350 kcmil177.3 mm²310 A12.88 V (10.73%)107.1 V21.24 V (17.7%)9013.3 WDrop/Amp High
400 kcmil202.7 mm²335 A11.26 V (9.39%)108.7 V18.58 V (15.48%)7883.9 WDrop/Amp High
500 kcmil253.4 mm²380 A9.01 V (7.51%)111.0 V14.86 V (12.38%)6306.5 WDrop/Amp High
600 kcmil304.0 mm²420 A7.51 V (6.26%)112.5 V12.39 V (10.32%)5256.8 WDrop/Amp High
750 kcmil380.0 mm²475 A6.01 V (5.01%)114.0 V9.91 V (8.26%)4205.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.51 V (3.75%)115.5 V7.43 V (6.19%)3153.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 250 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.25V (1.88%) and delivers 117.8V at the load.

What size aluminum wire is required for 700 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.43V (6.19%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.