⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.03%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.08V (3.4%)
Voltage at Load End205.8 VLoss: 2.15 V (2601.9 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1045.58 V (502.68%)0.0 V1724.72 V (829.19%)1267696.9 WDrop/Amp High
12 AWG3.31 mm²20 A657.04 V (315.88%)0.0 V1083.81 V (521.06%)796619.2 WDrop/Amp High
10 AWG5.26 mm²30 A413.46 V (198.78%)0.0 V682.02 V (327.89%)501294.6 WDrop/Amp High
8 AWG8.37 mm²50 A259.83 V (124.92%)0.0 V428.6 V (206.06%)315031.0 WDrop/Amp High
6 AWG13.3 mm²65 A163.52 V (78.61%)44.5 V269.73 V (129.68%)198256.4 WDrop/Amp High
4 AWG21.15 mm²85 A102.83 V (49.44%)105.2 V169.62 V (81.55%)124671.8 WDrop/Amp High
3 AWG26.67 mm²100 A81.54 V (39.2%)126.5 V134.51 V (64.67%)98868.0 WDrop/Amp High
2 AWG33.62 mm²115 A64.69 V (31.1%)143.3 V106.7 V (51.3%)78429.8 WDrop/Amp High
1 AWG42.41 mm²130 A51.28 V (24.65%)156.7 V84.59 V (40.67%)62174.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.66 V (19.55%)167.3 V67.07 V (32.24%)49295.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A32.25 V (15.51%)175.7 V53.2 V (25.58%)39104.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.58 V (12.3%)182.4 V42.2 V (20.29%)31017.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.29 V (9.75%)187.7 V33.46 V (16.09%)24597.1 WDrop/Amp High
250 kcmil126.7 mm²255 A17.16 V (8.25%)190.8 V28.31 V (13.61%)20811.4 WDrop/Amp High
300 kcmil152.0 mm²285 A14.31 V (6.88%)193.7 V23.6 V (11.35%)17347.4 WDrop/Amp High
350 kcmil177.3 mm²310 A12.27 V (5.9%)195.7 V20.23 V (9.73%)14872.0 WDrop/Amp High
400 kcmil202.7 mm²335 A10.73 V (5.16%)197.3 V17.7 V (8.51%)13008.4 WDrop/Amp High
500 kcmil253.4 mm²380 A8.58 V (4.13%)199.4 V14.16 V (6.81%)10405.7 WDrop/Amp High
600 kcmil304.0 mm²420 A7.15 V (3.44%)200.8 V11.8 V (5.67%)8673.7 WDrop/Amp High
750 kcmil380.0 mm²475 A5.72 V (2.75%)202.3 V9.44 V (4.54%)6939.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.29 V (2.06%)203.7 V7.08 V (3.4%)5203.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 275 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.15V (1.03%) and delivers 205.8V at the load.

What size aluminum wire is required for 700 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.08V (3.4%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.