🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 350 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.4V (8.67%)
Voltage at Load End116.8 VLoss: 3.15 V (2207.7 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 350 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1536.6 V (1280.5%)0.0 V2534.68 V (2112.23%)1075621.6 WDrop/Amp High
12 AWG3.31 mm²20 A965.6 V (804.67%)0.0 V1592.79 V (1327.32%)675919.3 WDrop/Amp High
10 AWG5.26 mm²30 A607.63 V (506.36%)0.0 V1002.31 V (835.25%)425340.9 WDrop/Amp High
8 AWG8.37 mm²50 A381.86 V (318.21%)0.0 V629.88 V (524.9%)267299.0 WDrop/Amp High
6 AWG13.3 mm²65 A240.31 V (200.26%)0.0 V396.4 V (330.33%)168217.5 WDrop/Amp High
4 AWG21.15 mm²85 A151.12 V (125.93%)0.0 V249.27 V (207.73%)105782.2 WDrop/Amp High
3 AWG26.67 mm²100 A119.84 V (99.87%)0.2 V197.68 V (164.73%)83888.0 WDrop/Amp High
2 AWG33.62 mm²115 A95.07 V (79.22%)24.9 V156.82 V (130.68%)66546.5 WDrop/Amp High
1 AWG42.41 mm²130 A75.36 V (62.8%)44.6 V124.31 V (103.59%)52753.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A59.75 V (49.79%)60.2 V98.56 V (82.14%)41826.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.4 V (39.5%)72.6 V78.19 V (65.16%)33179.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.6 V (31.33%)82.4 V62.02 V (51.68%)26318.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A29.81 V (24.85%)90.2 V49.18 V (40.98%)20870.3 WDrop/Amp High
250 kcmil126.7 mm²255 A25.23 V (21.02%)94.8 V41.61 V (34.68%)17658.2 WDrop/Amp High
300 kcmil152.0 mm²285 A21.03 V (17.52%)99.0 V34.69 V (28.9%)14719.0 WDrop/Amp High
350 kcmil177.3 mm²310 A18.03 V (15.02%)102.0 V29.74 V (24.78%)12618.7 WDrop/Amp High
400 kcmil202.7 mm²335 A15.77 V (13.14%)104.2 V26.01 V (21.67%)11037.5 WDrop/Amp High
500 kcmil253.4 mm²380 A12.61 V (10.51%)107.4 V20.81 V (17.34%)8829.1 WDrop/Amp High
600 kcmil304.0 mm²420 A10.51 V (8.76%)109.5 V17.34 V (14.45%)7359.5 WDrop/Amp High
750 kcmil380.0 mm²475 A8.41 V (7.01%)111.6 V13.87 V (11.56%)5887.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.31 V (5.26%)113.7 V10.4 V (8.67%)4415.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 350 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 350 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.15V (2.63%) and delivers 116.8V at the load.

What size aluminum wire is required for 700 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.4V (8.67%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.