🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.31%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.4V (4.34%)
Voltage at Load End236.8 VLoss: 3.15 V (2207.7 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1536.6 V (640.25%)0.0 V2534.68 V (1056.11%)1075621.6 WDrop/Amp High
12 AWG3.31 mm²20 A965.6 V (402.33%)0.0 V1592.79 V (663.66%)675919.3 WDrop/Amp High
10 AWG5.26 mm²30 A607.63 V (253.18%)0.0 V1002.31 V (417.63%)425340.9 WDrop/Amp High
8 AWG8.37 mm²50 A381.86 V (159.11%)0.0 V629.88 V (262.45%)267299.0 WDrop/Amp High
6 AWG13.3 mm²65 A240.31 V (100.13%)0.0 V396.4 V (165.17%)168217.5 WDrop/Amp High
4 AWG21.15 mm²85 A151.12 V (62.97%)88.9 V249.27 V (103.86%)105782.2 WDrop/Amp High
3 AWG26.67 mm²100 A119.84 V (49.93%)120.2 V197.68 V (82.37%)83888.0 WDrop/Amp High
2 AWG33.62 mm²115 A95.07 V (39.61%)144.9 V156.82 V (65.34%)66546.5 WDrop/Amp High
1 AWG42.41 mm²130 A75.36 V (31.4%)164.6 V124.31 V (51.8%)52753.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A59.75 V (24.9%)180.2 V98.56 V (41.07%)41826.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.4 V (19.75%)192.6 V78.19 V (32.58%)33179.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.6 V (15.67%)202.4 V62.02 V (25.84%)26318.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A29.81 V (12.42%)210.2 V49.18 V (20.49%)20870.3 WDrop/Amp High
250 kcmil126.7 mm²255 A25.23 V (10.51%)214.8 V41.61 V (17.34%)17658.2 WDrop/Amp High
300 kcmil152.0 mm²285 A21.03 V (8.76%)219.0 V34.69 V (14.45%)14719.0 WDrop/Amp High
350 kcmil177.3 mm²310 A18.03 V (7.51%)222.0 V29.74 V (12.39%)12618.7 WDrop/Amp High
400 kcmil202.7 mm²335 A15.77 V (6.57%)224.2 V26.01 V (10.84%)11037.5 WDrop/Amp High
500 kcmil253.4 mm²380 A12.61 V (5.26%)227.4 V20.81 V (8.67%)8829.1 WDrop/Amp High
600 kcmil304.0 mm²420 A10.51 V (4.38%)229.5 V17.34 V (7.23%)7359.5 WDrop/Amp High
750 kcmil380.0 mm²475 A8.41 V (3.5%)231.6 V13.87 V (5.78%)5887.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.31 V (2.63%)233.7 V10.4 V (4.34%)4415.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 350 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.15V (1.31%) and delivers 236.8V at the load.

What size aluminum wire is required for 700 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.4V (4.34%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.