🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 400 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.89V (4.95%)
Voltage at Load End236.4 VLoss: 3.6 V (2523.1 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1756.12 V (731.72%)0.0 V2896.77 V (1206.99%)1229281.8 WDrop/Amp High
12 AWG3.31 mm²20 A1103.54 V (459.81%)0.0 V1820.33 V (758.47%)772479.2 WDrop/Amp High
10 AWG5.26 mm²30 A694.43 V (289.35%)0.0 V1145.49 V (477.29%)486103.8 WDrop/Amp High
8 AWG8.37 mm²50 A436.41 V (181.84%)0.0 V719.87 V (299.94%)305484.6 WDrop/Amp High
6 AWG13.3 mm²65 A274.64 V (114.43%)0.0 V453.03 V (188.76%)192248.6 WDrop/Amp High
4 AWG21.15 mm²85 A172.71 V (71.96%)67.3 V284.88 V (118.7%)120893.9 WDrop/Amp High
3 AWG26.67 mm²100 A136.96 V (57.07%)103.0 V225.92 V (94.13%)95872.0 WDrop/Amp High
2 AWG33.62 mm²115 A108.65 V (45.27%)131.4 V179.22 V (74.67%)76053.1 WDrop/Amp High
1 AWG42.41 mm²130 A86.13 V (35.89%)153.9 V142.07 V (59.2%)60290.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A68.29 V (28.45%)171.7 V112.64 V (46.93%)47801.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A54.17 V (22.57%)185.8 V89.36 V (37.23%)37919.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.97 V (17.9%)197.0 V70.88 V (29.53%)30077.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.07 V (14.2%)205.9 V56.21 V (23.42%)23851.7 WDrop/Amp High
250 kcmil126.7 mm²255 A28.83 V (12.01%)211.2 V47.56 V (19.81%)20180.8 WDrop/Amp High
300 kcmil152.0 mm²285 A24.03 V (10.01%)216.0 V39.64 V (16.52%)16821.8 WDrop/Amp High
350 kcmil177.3 mm²310 A20.6 V (8.58%)219.4 V33.98 V (14.16%)14421.4 WDrop/Amp High
400 kcmil202.7 mm²335 A18.02 V (7.51%)222.0 V29.73 V (12.39%)12614.2 WDrop/Amp High
500 kcmil253.4 mm²380 A14.41 V (6.01%)225.6 V23.78 V (9.91%)10090.4 WDrop/Amp High
600 kcmil304.0 mm²420 A12.02 V (5.01%)228.0 V19.82 V (8.26%)8410.9 WDrop/Amp High
750 kcmil380.0 mm²475 A9.61 V (4.01%)230.4 V15.86 V (6.61%)6728.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.21 V (3.0%)232.8 V11.89 V (4.95%)5046.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 400 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.6V (1.5%) and delivers 236.4V at the load.

What size aluminum wire is required for 700 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.89V (4.95%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.