⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.59V (2.41%)
Voltage at Load End476.5 VLoss: 3.51 V (4257.8 W)
Power & Breaker (125%)581.97 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1710.95 V (356.45%)0.0 V2822.26 V (587.97%)2074413.1 WDrop/Amp High
12 AWG3.31 mm²20 A1075.16 V (223.99%)0.0 V1773.51 V (369.48%)1303558.7 WDrop/Amp High
10 AWG5.26 mm²30 A676.57 V (140.95%)0.0 V1116.03 V (232.51%)820300.2 WDrop/Amp High
8 AWG8.37 mm²50 A425.18 V (88.58%)54.8 V701.35 V (146.11%)515505.3 WDrop/Amp High
6 AWG13.3 mm²65 A267.58 V (55.75%)212.4 V441.38 V (91.95%)324419.5 WDrop/Amp High
4 AWG21.15 mm²85 A168.26 V (35.05%)311.7 V277.56 V (57.82%)204008.5 WDrop/Amp High
3 AWG26.67 mm²100 A133.44 V (27.8%)346.6 V220.11 V (45.86%)161784.0 WDrop/Amp High
2 AWG33.62 mm²115 A105.85 V (22.05%)374.1 V174.61 V (36.38%)128339.7 WDrop/Amp High
1 AWG42.41 mm²130 A83.91 V (17.48%)396.1 V138.42 V (28.84%)101739.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A66.53 V (13.86%)413.5 V109.75 V (22.86%)80665.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A52.78 V (11.0%)427.2 V87.06 V (18.14%)63989.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A41.86 V (8.72%)438.1 V69.05 V (14.39%)50756.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.2 V (6.92%)446.8 V54.76 V (11.41%)40249.8 WDrop/Amp High
250 kcmil126.7 mm²255 A28.09 V (5.85%)451.9 V46.33 V (9.65%)34055.1 WDrop/Amp High
300 kcmil152.0 mm²285 A23.41 V (4.88%)456.6 V38.62 V (8.05%)28386.7 WDrop/Amp High
350 kcmil177.3 mm²310 A20.07 V (4.18%)459.9 V33.11 V (6.9%)24336.0 WDrop/Amp High
400 kcmil202.7 mm²335 A17.56 V (3.66%)462.4 V28.96 V (6.03%)21286.5 WDrop/Amp High
500 kcmil253.4 mm²380 A14.04 V (2.93%)466.0 V23.17 V (4.83%)17027.5 WDrop/Amp High
600 kcmil304.0 mm²420 A11.71 V (2.44%)468.3 V19.31 V (4.02%)14193.4 WDrop/Amp High
750 kcmil380.0 mm²475 A9.37 V (1.95%)470.6 V15.45 V (3.22%)11354.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.02 V (1.46%)473.0 V11.59 V (2.41%)8515.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 450 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.51V (0.73%) and delivers 476.5V at the load.

What size aluminum wire is required for 700 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.59V (2.41%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.