🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.78V (19.82%)
Voltage at Load End117.1 VLoss: 2.88 V (2018.5 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3512.23 V (2926.86%)0.0 V5793.54 V (4827.95%)2458563.7 WDrop/Amp High
12 AWG3.31 mm²20 A2207.08 V (1839.24%)0.0 V3640.66 V (3033.88%)1544958.5 WDrop/Amp High
10 AWG5.26 mm²30 A1388.87 V (1157.39%)0.0 V2290.98 V (1909.15%)972207.7 WDrop/Amp High
8 AWG8.37 mm²50 A872.81 V (727.34%)0.0 V1439.73 V (1199.78%)610969.2 WDrop/Amp High
6 AWG13.3 mm²65 A549.28 V (457.73%)0.0 V906.06 V (755.05%)384497.2 WDrop/Amp High
4 AWG21.15 mm²85 A345.41 V (287.84%)0.0 V569.77 V (474.81%)241787.8 WDrop/Amp High
3 AWG26.67 mm²100 A273.92 V (228.27%)0.0 V451.84 V (376.53%)191744.0 WDrop/Amp High
2 AWG33.62 mm²115 A217.29 V (181.08%)0.0 V358.43 V (298.7%)152106.3 WDrop/Amp High
1 AWG42.41 mm²130 A172.26 V (143.55%)0.0 V284.14 V (236.79%)120580.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A136.58 V (113.81%)0.0 V225.29 V (187.74%)95603.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A108.34 V (90.28%)11.7 V178.71 V (148.93%)75838.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A85.94 V (71.61%)34.1 V141.75 V (118.13%)60155.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A68.15 V (56.79%)51.9 V112.41 V (93.68%)47703.5 WDrop/Amp High
250 kcmil126.7 mm²255 A57.66 V (48.05%)62.3 V95.11 V (79.26%)40361.6 WDrop/Amp High
300 kcmil152.0 mm²285 A48.06 V (40.05%)71.9 V79.28 V (66.07%)33643.5 WDrop/Amp High
350 kcmil177.3 mm²310 A41.2 V (34.34%)78.8 V67.97 V (56.64%)28842.7 WDrop/Amp High
400 kcmil202.7 mm²335 A36.04 V (30.03%)84.0 V59.45 V (49.54%)25228.5 WDrop/Amp High
500 kcmil253.4 mm²380 A28.83 V (24.02%)91.2 V47.56 V (39.63%)20180.8 WDrop/Amp High
600 kcmil304.0 mm²420 A24.03 V (20.03%)96.0 V39.64 V (33.03%)16821.8 WDrop/Amp High
750 kcmil380.0 mm²475 A19.22 V (16.02%)100.8 V31.71 V (26.43%)13457.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.42 V (12.01%)105.6 V23.78 V (19.82%)10092.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 800 feet one-way at 120V (1-Phase), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.88V (2.4%) and delivers 117.1V at the load.

What size aluminum wire is required for 700 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.78V (19.82%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.