750 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.65V (4.02%)
Voltage at Load End237.1 VLoss: 2.92 V (3801.6 W)
Power & Breaker (125%)311.77 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1425.79 V (594.08%)0.0 V2351.89 V (979.95%)1852154.6 WDrop/Amp High
12 AWG3.31 mm²20 A895.96 V (373.32%)0.0 V1477.92 V (615.8%)1163891.7 WDrop/Amp High
10 AWG5.26 mm²30 A563.81 V (234.92%)0.0 V930.02 V (387.51%)732410.9 WDrop/Amp High
8 AWG8.37 mm²50 A354.32 V (147.63%)0.0 V584.46 V (243.52%)460272.6 WDrop/Amp High
6 AWG13.3 mm²65 A222.98 V (92.91%)17.0 V367.81 V (153.26%)289660.3 WDrop/Amp High
4 AWG21.15 mm²85 A140.22 V (58.42%)99.8 V231.3 V (96.37%)182150.4 WDrop/Amp High
3 AWG26.67 mm²100 A111.2 V (46.33%)128.8 V183.42 V (76.43%)144450.0 WDrop/Amp High
2 AWG33.62 mm²115 A88.21 V (36.75%)151.8 V145.51 V (60.63%)114589.0 WDrop/Amp High
1 AWG42.41 mm²130 A69.93 V (29.14%)170.1 V115.35 V (48.06%)90839.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A55.44 V (23.1%)184.6 V91.45 V (38.11%)72022.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.98 V (18.33%)196.0 V72.55 V (30.23%)57133.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.89 V (14.54%)205.1 V57.55 V (23.98%)45318.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.66 V (11.53%)212.3 V45.63 V (19.01%)35937.3 WDrop/Amp High
250 kcmil126.7 mm²255 A23.41 V (9.75%)216.6 V38.61 V (16.09%)30406.3 WDrop/Amp High
300 kcmil152.0 mm²285 A19.51 V (8.13%)220.5 V32.18 V (13.41%)25345.3 WDrop/Amp High
350 kcmil177.3 mm²310 A16.73 V (6.97%)223.3 V27.59 V (11.5%)21728.6 WDrop/Amp High
400 kcmil202.7 mm²335 A14.63 V (6.1%)225.4 V24.13 V (10.06%)19005.8 WDrop/Amp High
500 kcmil253.4 mm²380 A11.7 V (4.88%)228.3 V19.31 V (8.04%)15203.2 WDrop/Amp High
600 kcmil304.0 mm²420 A9.76 V (4.06%)230.2 V16.09 V (6.7%)12672.6 WDrop/Amp High
750 kcmil380.0 mm²475 A7.8 V (3.25%)232.2 V12.87 V (5.36%)10138.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.85 V (2.44%)234.1 V9.65 V (4.02%)7603.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 350 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.92V (1.22%) and delivers 237.1V at the load.

What size aluminum wire is required for 750 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.65V (4.02%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.