⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 250 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.49V (7.08%)
Voltage at Load End117.4 VLoss: 2.58 V (2059.7 W)
Power & Breaker (125%)96.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 250 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1254.37 V (1045.31%)0.0 V2069.12 V (1724.27%)1003495.4 WDrop/Amp High
12 AWG3.31 mm²20 A788.24 V (656.87%)0.0 V1300.23 V (1083.53%)630595.3 WDrop/Amp High
10 AWG5.26 mm²30 A496.02 V (413.35%)0.0 V818.21 V (681.84%)396819.5 WDrop/Amp High
8 AWG8.37 mm²50 A311.72 V (259.77%)0.0 V514.19 V (428.49%)249375.2 WDrop/Amp High
6 AWG13.3 mm²65 A196.17 V (163.48%)0.0 V323.59 V (269.66%)156937.6 WDrop/Amp High
4 AWG21.15 mm²85 A123.36 V (102.8%)0.0 V203.49 V (169.57%)98688.9 WDrop/Amp High
3 AWG26.67 mm²100 A97.83 V (81.52%)22.2 V161.37 V (134.48%)78262.9 WDrop/Amp High
2 AWG33.62 mm²115 A77.61 V (64.67%)42.4 V128.01 V (106.68%)62084.2 WDrop/Amp High
1 AWG42.41 mm²130 A61.52 V (51.27%)58.5 V101.48 V (84.57%)49216.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A48.78 V (40.65%)71.2 V80.46 V (67.05%)39021.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A38.69 V (32.24%)81.3 V63.83 V (53.19%)30954.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A30.69 V (25.58%)89.3 V50.63 V (42.19%)24553.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A24.34 V (20.28%)95.7 V40.15 V (33.46%)19470.8 WDrop/Amp High
250 kcmil126.7 mm²255 A20.59 V (17.16%)99.4 V33.97 V (28.31%)16474.1 WDrop/Amp High
300 kcmil152.0 mm²285 A17.17 V (14.3%)102.8 V28.31 V (23.6%)13732.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.72 V (12.26%)105.3 V24.27 V (20.23%)11772.5 WDrop/Amp High
400 kcmil202.7 mm²335 A12.87 V (10.73%)107.1 V21.23 V (17.69%)10297.3 WDrop/Amp High
500 kcmil253.4 mm²380 A10.3 V (8.58%)109.7 V16.98 V (14.15%)8237.1 WDrop/Amp High
600 kcmil304.0 mm²420 A8.58 V (7.15%)111.4 V14.16 V (11.8%)6866.0 WDrop/Amp High
750 kcmil380.0 mm²475 A6.87 V (5.72%)113.1 V11.33 V (9.44%)5492.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.15 V (4.29%)114.9 V8.49 V (7.08%)4119.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 250 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 250 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.58V (2.15%) and delivers 117.4V at the load.

What size aluminum wire is required for 800 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.49V (7.08%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.