⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 500 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.99V (7.08%)
Voltage at Load End234.8 VLoss: 5.15 V (4119.4 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2508.74 V (1045.31%)0.0 V4138.25 V (1724.27%)2006990.8 WDrop/Amp High
12 AWG3.31 mm²20 A1576.49 V (656.87%)0.0 V2600.47 V (1083.53%)1261190.6 WDrop/Amp High
10 AWG5.26 mm²30 A992.05 V (413.35%)0.0 V1636.42 V (681.84%)793638.9 WDrop/Amp High
8 AWG8.37 mm²50 A623.44 V (259.77%)0.0 V1028.38 V (428.49%)498750.4 WDrop/Amp High
6 AWG13.3 mm²65 A392.34 V (163.48%)0.0 V647.18 V (269.66%)313875.2 WDrop/Amp High
4 AWG21.15 mm²85 A246.72 V (102.8%)0.0 V406.98 V (169.57%)197377.8 WDrop/Amp High
3 AWG26.67 mm²100 A195.66 V (81.52%)44.3 V322.74 V (134.48%)156525.7 WDrop/Amp High
2 AWG33.62 mm²115 A155.21 V (64.67%)84.8 V256.02 V (106.68%)124168.4 WDrop/Amp High
1 AWG42.41 mm²130 A123.04 V (51.27%)117.0 V202.96 V (84.57%)98432.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A97.55 V (40.65%)142.4 V160.92 V (67.05%)78043.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A77.39 V (32.24%)162.6 V127.65 V (53.19%)61909.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A61.38 V (25.58%)178.6 V101.25 V (42.19%)49106.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A48.68 V (20.28%)191.3 V80.29 V (33.46%)38941.6 WDrop/Amp High
250 kcmil126.7 mm²255 A41.19 V (17.16%)198.8 V67.94 V (28.31%)32948.2 WDrop/Amp High
300 kcmil152.0 mm²285 A34.33 V (14.3%)205.7 V56.63 V (23.6%)27464.1 WDrop/Amp High
350 kcmil177.3 mm²310 A29.43 V (12.26%)210.6 V48.55 V (20.23%)23545.1 WDrop/Amp High
400 kcmil202.7 mm²335 A25.74 V (10.73%)214.3 V42.46 V (17.69%)20594.7 WDrop/Amp High
500 kcmil253.4 mm²380 A20.59 V (8.58%)219.4 V33.97 V (14.15%)16474.1 WDrop/Amp High
600 kcmil304.0 mm²420 A17.17 V (7.15%)222.8 V28.31 V (11.8%)13732.0 WDrop/Amp High
750 kcmil380.0 mm²475 A13.73 V (5.72%)226.3 V22.65 V (9.44%)10985.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.3 V (4.29%)229.7 V16.99 V (7.08%)8238.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 500 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.15V (2.15%) and delivers 234.8V at the load.

What size aluminum wire is required for 800 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.99V (7.08%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.