900 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.97V (0.83%)
Voltage at Load End478.8 VLoss: 1.21 V (1876.9 W)
Power & Breaker (125%)748.25 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A586.61 V (122.21%)0.0 V967.63 V (201.59%)914435.2 WDrop/Amp High
12 AWG3.31 mm²20 A368.63 V (76.8%)111.4 V608.06 V (126.68%)574630.0 WDrop/Amp High
10 AWG5.26 mm²30 A231.97 V (48.33%)248.0 V382.64 V (79.72%)361601.7 WDrop/Amp High
8 AWG8.37 mm²50 A145.78 V (30.37%)334.2 V240.46 V (50.1%)227243.1 WDrop/Amp High
6 AWG13.3 mm²65 A91.74 V (19.11%)388.3 V151.33 V (31.53%)143009.4 WDrop/Amp High
4 AWG21.15 mm²85 A57.69 V (12.02%)422.3 V95.16 V (19.83%)89930.3 WDrop/Amp High
3 AWG26.67 mm²100 A45.75 V (9.53%)434.3 V75.47 V (15.72%)71317.0 WDrop/Amp High
2 AWG33.62 mm²115 A36.29 V (7.56%)443.7 V59.87 V (12.47%)56574.2 WDrop/Amp High
1 AWG42.41 mm²130 A28.77 V (5.99%)451.2 V47.46 V (9.89%)44848.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.81 V (4.75%)457.2 V37.63 V (7.84%)35558.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.1 V (3.77%)461.9 V29.85 V (6.22%)28207.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.35 V (2.99%)465.6 V23.68 V (4.93%)22374.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.38 V (2.37%)468.6 V18.77 V (3.91%)17742.8 WDrop/Amp High
250 kcmil126.7 mm²255 A9.63 V (2.01%)470.4 V15.89 V (3.31%)15012.0 WDrop/Amp High
300 kcmil152.0 mm²285 A8.03 V (1.67%)472.0 V13.24 V (2.76%)12513.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.88 V (1.43%)473.1 V11.35 V (2.36%)10727.7 WDrop/Amp High
400 kcmil202.7 mm²335 A6.02 V (1.25%)474.0 V9.93 V (2.07%)9383.4 WDrop/Amp High
500 kcmil253.4 mm²380 A4.82 V (1.0%)475.2 V7.94 V (1.65%)7506.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.01 V (0.84%)476.0 V6.62 V (1.38%)6256.7 WDrop/Amp High
750 kcmil380.0 mm²475 A3.21 V (0.67%)476.8 V5.3 V (1.1%)5005.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.41 V (0.5%)477.6 V3.97 V (0.83%)3753.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 120 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.21V (0.25%) and delivers 478.8V at the load.

What size aluminum wire is required for 900 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.97V (0.83%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.