🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.65V (0.55%)
Voltage at Load End479.2 VLoss: 0.81 V (1251.2 W)
Power & Breaker (125%)748.25 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A391.07 V (81.47%)88.9 V645.09 V (134.39%)609623.4 WDrop/Amp High
12 AWG3.31 mm²20 A245.75 V (51.2%)234.2 V405.37 V (84.45%)383086.6 WDrop/Amp High
10 AWG5.26 mm²30 A154.65 V (32.22%)325.4 V255.09 V (53.14%)241067.8 WDrop/Amp High
8 AWG8.37 mm²50 A97.18 V (20.25%)382.8 V160.31 V (33.4%)151495.4 WDrop/Amp High
6 AWG13.3 mm²65 A61.16 V (12.74%)418.8 V100.89 V (21.02%)95339.6 WDrop/Amp High
4 AWG21.15 mm²85 A38.46 V (8.01%)441.5 V63.44 V (13.22%)59953.5 WDrop/Amp High
3 AWG26.67 mm²100 A30.5 V (6.35%)449.5 V50.31 V (10.48%)47544.7 WDrop/Amp High
2 AWG33.62 mm²115 A24.19 V (5.04%)455.8 V39.91 V (8.31%)37716.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.18 V (4.0%)460.8 V31.64 V (6.59%)29899.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.21 V (3.17%)464.8 V25.08 V (5.23%)23705.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.06 V (2.51%)467.9 V19.9 V (4.15%)18804.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.57 V (1.99%)470.4 V15.78 V (3.29%)14916.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.59 V (1.58%)472.4 V12.52 V (2.61%)11828.5 WDrop/Amp High
250 kcmil126.7 mm²255 A6.42 V (1.34%)473.6 V10.59 V (2.21%)10008.0 WDrop/Amp High
300 kcmil152.0 mm²285 A5.35 V (1.11%)474.6 V8.83 V (1.84%)8342.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.59 V (0.96%)475.4 V7.57 V (1.58%)7151.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.01 V (0.84%)476.0 V6.62 V (1.38%)6255.6 WDrop/Amp High
500 kcmil253.4 mm²380 A3.21 V (0.67%)476.8 V5.3 V (1.1%)5004.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.68 V (0.56%)477.3 V4.41 V (0.92%)4171.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.14 V (0.45%)477.9 V3.53 V (0.74%)3336.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.61 V (0.33%)478.4 V2.65 V (0.55%)2502.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 80 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.81V (0.17%) and delivers 479.2V at the load.

What size aluminum wire is required for 900 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.65V (0.55%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.