⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 60 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.99V (0.41%)
Voltage at Load End479.4 VLoss: 0.6 V (938.5 W)
Power & Breaker (125%)748.25 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 60 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A293.31 V (61.11%)186.7 V483.82 V (100.8%)457217.6 WDrop/Amp High
12 AWG3.31 mm²20 A184.31 V (38.4%)295.7 V304.03 V (63.34%)287315.0 WDrop/Amp High
10 AWG5.26 mm²30 A115.98 V (24.16%)364.0 V191.32 V (39.86%)180800.9 WDrop/Amp High
8 AWG8.37 mm²50 A72.89 V (15.19%)407.1 V120.23 V (25.05%)113621.6 WDrop/Amp High
6 AWG13.3 mm²65 A45.87 V (9.56%)434.1 V75.66 V (15.76%)71504.7 WDrop/Amp High
4 AWG21.15 mm²85 A28.85 V (6.01%)451.2 V47.58 V (9.91%)44965.1 WDrop/Amp High
3 AWG26.67 mm²100 A22.87 V (4.77%)457.1 V37.73 V (7.86%)35658.5 WDrop/Amp High
2 AWG33.62 mm²115 A18.15 V (3.78%)461.9 V29.93 V (6.24%)28287.1 WDrop/Amp High
1 AWG42.41 mm²130 A14.39 V (3.0%)465.6 V23.73 V (4.94%)22424.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.41 V (2.38%)468.6 V18.81 V (3.92%)17779.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.05 V (1.88%)471.0 V14.92 V (3.11%)14103.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.18 V (1.5%)472.8 V11.84 V (2.47%)11187.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.69 V (1.19%)474.3 V9.39 V (1.96%)8871.4 WDrop/Amp High
250 kcmil126.7 mm²255 A4.82 V (1.0%)475.2 V7.94 V (1.65%)7506.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.01 V (0.84%)476.0 V6.62 V (1.38%)6256.7 WDrop/Amp High
350 kcmil177.3 mm²310 A3.44 V (0.72%)476.6 V5.68 V (1.18%)5363.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.01 V (0.63%)477.0 V4.96 V (1.03%)4691.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.41 V (0.5%)477.6 V3.97 V (0.83%)3753.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.01 V (0.42%)478.0 V3.31 V (0.69%)3128.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.61 V (0.33%)478.4 V2.65 V (0.55%)2502.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.2 V (0.25%)478.8 V1.99 V (0.41%)1876.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 60 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 60 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.6V (0.12%) and delivers 479.4V at the load.

What size aluminum wire is required for 900 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.99V (0.41%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.