⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 50 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.1%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.66V (0.34%)
Voltage at Load End479.5 VLoss: 0.5 V (782.0 W)
Power & Breaker (125%)748.25 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 50 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A244.42 V (50.92%)235.6 V403.18 V (84.0%)381014.7 WDrop/Amp High
12 AWG3.31 mm²20 A153.59 V (32.0%)326.4 V253.36 V (52.78%)239429.1 WDrop/Amp High
10 AWG5.26 mm²30 A96.65 V (20.14%)383.3 V159.43 V (33.22%)150667.4 WDrop/Amp High
8 AWG8.37 mm²50 A60.74 V (12.65%)419.3 V100.19 V (20.87%)94684.6 WDrop/Amp High
6 AWG13.3 mm²65 A38.23 V (7.96%)441.8 V63.05 V (13.14%)59587.3 WDrop/Amp High
4 AWG21.15 mm²85 A24.04 V (5.01%)456.0 V39.65 V (8.26%)37470.9 WDrop/Amp High
3 AWG26.67 mm²100 A19.06 V (3.97%)460.9 V31.44 V (6.55%)29715.4 WDrop/Amp High
2 AWG33.62 mm²115 A15.12 V (3.15%)464.9 V24.94 V (5.2%)23572.6 WDrop/Amp High
1 AWG42.41 mm²130 A11.99 V (2.5%)468.0 V19.77 V (4.12%)18686.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.5 V (1.98%)470.5 V15.68 V (3.27%)14816.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.54 V (1.57%)472.5 V12.44 V (2.59%)11753.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.98 V (1.25%)474.0 V9.86 V (2.06%)9322.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.74 V (0.99%)475.3 V7.82 V (1.63%)7392.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.01 V (0.84%)476.0 V6.62 V (1.38%)6255.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.34 V (0.7%)476.7 V5.52 V (1.15%)5213.9 WDrop/Amp High
350 kcmil177.3 mm²310 A2.87 V (0.6%)477.1 V4.73 V (0.99%)4469.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.51 V (0.52%)477.5 V4.14 V (0.86%)3909.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.01 V (0.42%)478.0 V3.31 V (0.69%)3127.5 WDrop/Amp High
600 kcmil304.0 mm²420 A1.67 V (0.35%)478.3 V2.76 V (0.57%)2606.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.34 V (0.28%)478.7 V2.21 V (0.46%)2085.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.0 V (0.21%)479.0 V1.66 V (0.34%)1564.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 50 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 50 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.5V (0.1%) and delivers 479.5V at the load.

What size aluminum wire is required for 900 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.66V (0.34%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.