⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 275 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.65%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.51V (8.76%)
Voltage at Load End116.8 VLoss: 3.19 V (2867.4 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 275 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1552.28 V (1293.57%)0.0 V2560.54 V (2133.78%)1397053.7 WDrop/Amp High
12 AWG3.31 mm²20 A975.45 V (812.88%)0.0 V1609.04 V (1340.87%)877906.9 WDrop/Amp High
10 AWG5.26 mm²30 A613.83 V (511.53%)0.0 V1012.53 V (843.78%)552447.1 WDrop/Amp High
8 AWG8.37 mm²50 A385.75 V (321.46%)0.0 V636.31 V (530.26%)347177.0 WDrop/Amp High
6 AWG13.3 mm²65 A242.76 V (202.3%)0.0 V400.45 V (333.7%)218486.6 WDrop/Amp High
4 AWG21.15 mm²85 A152.66 V (127.22%)0.0 V251.82 V (209.85%)137393.5 WDrop/Amp High
3 AWG26.67 mm²100 A121.06 V (100.89%)0.0 V199.7 V (166.41%)108956.6 WDrop/Amp High
2 AWG33.62 mm²115 A96.04 V (80.03%)24.0 V158.42 V (132.01%)86432.8 WDrop/Amp High
1 AWG42.41 mm²130 A76.13 V (63.44%)43.9 V125.58 V (104.65%)68518.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A60.36 V (50.3%)59.6 V99.57 V (82.97%)54325.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A47.88 V (39.9%)72.1 V78.98 V (65.82%)43094.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A37.98 V (31.65%)82.0 V62.65 V (52.21%)34182.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A30.12 V (25.1%)89.9 V49.68 V (41.4%)27107.0 WDrop/Amp High
250 kcmil126.7 mm²255 A25.48 V (21.24%)94.5 V42.04 V (35.03%)22935.1 WDrop/Amp High
300 kcmil152.0 mm²285 A21.24 V (17.7%)98.8 V35.04 V (29.2%)19117.6 WDrop/Amp High
350 kcmil177.3 mm²310 A18.21 V (15.18%)101.8 V30.04 V (25.03%)16389.6 WDrop/Amp High
400 kcmil202.7 mm²335 A15.93 V (13.27%)104.1 V26.27 V (21.9%)14335.8 WDrop/Amp High
500 kcmil253.4 mm²380 A12.74 V (10.62%)107.3 V21.02 V (17.51%)11467.5 WDrop/Amp High
600 kcmil304.0 mm²420 A10.62 V (8.85%)109.4 V17.52 V (14.6%)9558.8 WDrop/Amp High
750 kcmil380.0 mm²475 A8.5 V (7.08%)111.5 V14.02 V (11.68%)7647.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.37 V (5.31%)113.6 V10.51 V (8.76%)5734.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 275 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 275 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.19V (2.65%) and delivers 116.8V at the load.

What size aluminum wire is required for 900 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.51V (8.76%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.