🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.51%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.86V (8.28%)
Voltage at Load End234.0 VLoss: 6.02 V (9384.4 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2933.05 V (1222.11%)0.0 V4838.17 V (2015.9%)4572175.8 WDrop/Amp High
12 AWG3.31 mm²20 A1843.13 V (767.97%)0.0 V3040.3 V (1266.79%)2873149.8 WDrop/Amp High
10 AWG5.26 mm²30 A1159.84 V (483.27%)0.0 V1913.19 V (797.16%)1808008.7 WDrop/Amp High
8 AWG8.37 mm²50 A728.88 V (303.7%)0.0 V1202.32 V (500.96%)1136215.7 WDrop/Amp High
6 AWG13.3 mm²65 A458.7 V (191.13%)0.0 V756.65 V (315.27%)715047.0 WDrop/Amp High
4 AWG21.15 mm²85 A288.45 V (120.19%)0.0 V475.81 V (198.25%)449651.3 WDrop/Amp High
3 AWG26.67 mm²100 A228.75 V (95.31%)11.3 V377.33 V (157.22%)356585.1 WDrop/Amp High
2 AWG33.62 mm²115 A181.46 V (75.61%)58.5 V299.33 V (124.72%)282871.1 WDrop/Amp High
1 AWG42.41 mm²130 A143.85 V (59.94%)96.1 V237.29 V (98.87%)224242.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A114.05 V (47.52%)125.9 V188.14 V (78.39%)177792.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A90.48 V (37.7%)149.5 V149.24 V (62.18%)141037.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A71.77 V (29.9%)168.2 V118.38 V (49.32%)111870.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A56.91 V (23.71%)183.1 V93.87 V (39.11%)88713.9 WDrop/Amp High
250 kcmil126.7 mm²255 A48.15 V (20.06%)191.8 V79.43 V (33.09%)75060.2 WDrop/Amp High
300 kcmil152.0 mm²285 A40.14 V (16.72%)199.9 V66.21 V (27.59%)62566.6 WDrop/Amp High
350 kcmil177.3 mm²310 A34.41 V (14.34%)205.6 V56.76 V (23.65%)53638.6 WDrop/Amp High
400 kcmil202.7 mm²335 A30.1 V (12.54%)209.9 V49.65 V (20.69%)46917.2 WDrop/Amp High
500 kcmil253.4 mm²380 A24.08 V (10.03%)215.9 V39.71 V (16.55%)37530.1 WDrop/Amp High
600 kcmil304.0 mm²420 A20.07 V (8.36%)219.9 V33.1 V (13.79%)31283.3 WDrop/Amp High
750 kcmil380.0 mm²475 A16.05 V (6.69%)223.9 V26.48 V (11.03%)25026.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.04 V (5.02%)228.0 V19.86 V (8.28%)18768.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 600 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.02V (2.51%) and delivers 234.0V at the load.

What size aluminum wire is required for 900 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.86V (8.28%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.