🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 24.83V (10.34%)
Voltage at Load End235.0 VLoss: 5.02 V (7820.3 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3666.32 V (1527.63%)0.0 V6047.71 V (2519.88%)5715219.8 WDrop/Amp High
12 AWG3.31 mm²20 A2303.91 V (959.96%)0.0 V3800.37 V (1583.49%)3591437.2 WDrop/Amp High
10 AWG5.26 mm²30 A1449.8 V (604.08%)0.0 V2391.49 V (996.45%)2260010.9 WDrop/Amp High
8 AWG8.37 mm²50 A911.1 V (379.63%)0.0 V1502.89 V (626.21%)1420269.7 WDrop/Amp High
6 AWG13.3 mm²65 A573.38 V (238.91%)0.0 V945.81 V (394.09%)893808.8 WDrop/Amp High
4 AWG21.15 mm²85 A360.56 V (150.24%)0.0 V594.76 V (247.82%)562064.2 WDrop/Amp High
3 AWG26.67 mm²100 A285.94 V (119.14%)0.0 V471.66 V (196.53%)445731.4 WDrop/Amp High
2 AWG33.62 mm²115 A226.83 V (94.51%)13.2 V374.16 V (155.9%)353588.9 WDrop/Amp High
1 AWG42.41 mm²130 A179.81 V (74.92%)60.2 V296.61 V (123.59%)280303.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A142.57 V (59.4%)97.4 V235.17 V (97.99%)222240.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A113.09 V (47.12%)126.9 V186.55 V (77.73%)176296.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A89.71 V (37.38%)150.3 V147.97 V (61.66%)139838.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A71.14 V (29.64%)168.9 V117.34 V (48.89%)110892.3 WDrop/Amp High
250 kcmil126.7 mm²255 A60.19 V (25.08%)179.8 V99.28 V (41.37%)93825.2 WDrop/Amp High
300 kcmil152.0 mm²285 A50.17 V (20.9%)189.8 V82.76 V (34.48%)78208.3 WDrop/Amp High
350 kcmil177.3 mm²310 A43.01 V (17.92%)197.0 V70.95 V (29.56%)67048.3 WDrop/Amp High
400 kcmil202.7 mm²335 A37.62 V (15.68%)202.4 V62.06 V (25.86%)58646.6 WDrop/Amp High
500 kcmil253.4 mm²380 A30.09 V (12.54%)209.9 V49.64 V (20.68%)46912.6 WDrop/Amp High
600 kcmil304.0 mm²420 A25.09 V (10.45%)214.9 V41.38 V (17.24%)39104.1 WDrop/Amp High
750 kcmil380.0 mm²475 A20.07 V (8.36%)219.9 V33.1 V (13.79%)31283.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A15.05 V (6.27%)224.9 V24.83 V (10.34%)23460.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 750 feet one-way at 240V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.02V (2.09%) and delivers 235.0V at the load.

What size aluminum wire is required for 900 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 24.83V (10.34%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.