1000 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 18.54V (2.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 61.14V (8.86%)
Voltage at Load671.5 VLine Loss: 32100.0 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9884.24 V (1432.5%)0.0 V16304.37 V (2362.95%)17120000.0 WDrop High
2.5 mm²24 A18 A5930.54 V (859.5%)0.0 V9782.62 V (1417.77%)10272000.0 WDrop High
4 mm²32 A25 A3706.59 V (537.19%)0.0 V6114.14 V (886.11%)6420000.0 WDrop High
6 mm²41 A32 A2471.06 V (358.12%)0.0 V4076.09 V (590.74%)4280000.0 WDrop High
10 mm²57 A44 A1482.64 V (214.87%)0.0 V2445.66 V (354.44%)2568000.0 WDrop High
16 mm²76 A59 A926.65 V (134.3%)0.0 V1528.53 V (221.53%)1605000.0 WDrop High
25 mm²101 A78 A593.05 V (85.95%)96.9 V978.26 V (141.78%)1027200.0 WDrop High
35 mm²125 A97 A423.61 V (61.39%)266.4 V698.76 V (101.27%)733714.3 WDrop High
50 mm²151 A118 A296.53 V (42.97%)393.5 V489.13 V (70.89%)513600.0 WDrop High
70 mm²192 A150 A211.81 V (30.7%)478.2 V349.38 V (50.63%)366857.1 WDrop High
95 mm²232 A181 A156.07 V (22.62%)533.9 V257.44 V (37.31%)270315.8 WDrop High
120 mm²269 A210 A123.55 V (17.91%)566.4 V203.8 V (29.54%)214000.0 WDrop High
150 mm²309 A241 A98.84 V (14.32%)591.2 V163.04 V (23.63%)171200.0 WDrop High
185 mm²353 A275 A80.14 V (11.61%)609.9 V132.2 V (19.16%)138810.8 WDrop High
240 mm²415 A324 A61.78 V (8.95%)628.2 V101.9 V (14.77%)107000.0 WDrop High
300 mm²477 A372 A49.42 V (7.16%)640.6 V81.52 V (11.81%)85600.0 WDrop High
400 mm²570 A445 A37.07 V (5.37%)652.9 V61.14 V (8.86%)64200.0 WDrop High

FAQ — 1000 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 400m at 690V (voltage drop: 18.54V or 2.69%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.