⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

15 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 10.03V (2.42%)
Voltage at Load405.3 VLine Loss: 252.8 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A64.87 V (15.63%)350.1 V107.0 V (25.78%)1685.2 WDrop High
2.5 mm²24 A18 A38.92 V (9.38%)376.1 V64.2 V (15.47%)1011.1 WDrop High
4 mm²32 A25 A24.32 V (5.86%)390.7 V40.12 V (9.67%)632.0 WDrop High
6 mm²41 A32 A16.22 V (3.91%)398.8 V26.75 V (6.45%)421.3 W~ ≤5%
10 mm²57 A44 A9.73 V (2.34%)405.3 V16.05 V (3.87%)252.8 W✓ OK (≤3%)
16 mm²76 A59 A6.08 V (1.47%)408.9 V10.03 V (2.42%)158.0 W✓ OK (≤3%)
25 mm²101 A78 A3.89 V (0.94%)411.1 V6.42 V (1.55%)101.1 W✓ OK (≤3%)
35 mm²125 A97 A2.78 V (0.67%)412.2 V4.59 V (1.1%)72.2 W✓ OK (≤3%)
50 mm²151 A118 A1.95 V (0.47%)413.1 V3.21 V (0.77%)50.6 W✓ OK (≤3%)
70 mm²192 A150 A1.39 V (0.33%)413.6 V2.29 V (0.55%)36.1 W✓ OK (≤3%)
95 mm²232 A181 A1.02 V (0.25%)414.0 V1.69 V (0.41%)26.6 W✓ OK (≤3%)
120 mm²269 A210 A0.81 V (0.2%)414.2 V1.34 V (0.32%)21.1 W✓ OK (≤3%)
150 mm²309 A241 A0.65 V (0.16%)414.4 V1.07 V (0.26%)16.9 W✓ OK (≤3%)
185 mm²353 A275 A0.53 V (0.13%)414.5 V0.87 V (0.21%)13.7 W✓ OK (≤3%)
240 mm²415 A324 A0.41 V (0.1%)414.6 V0.67 V (0.16%)10.5 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.08%)414.7 V0.53 V (0.13%)8.4 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.06%)414.8 V0.4 V (0.1%)6.3 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 15A over 175m at 415V (voltage drop: 9.73V or 2.34%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.