⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

30 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 20.5 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A68.48 V (285.33%)0.0 V112.96 V (470.67%)2054.4 WDrop High
2.5 mm²24 A18 A41.09 V (171.2%)0.0 V67.78 V (282.4%)1232.6 WDrop High
4 mm²32 A25 A25.68 V (107.0%)0.0 V42.36 V (176.5%)770.4 WDrop High
6 mm²41 A32 A17.12 V (71.33%)6.9 V28.24 V (117.67%)513.6 WDrop High
10 mm²57 A44 A10.27 V (42.8%)13.7 V16.94 V (70.6%)308.2 WDrop High
16 mm²76 A59 A6.42 V (26.75%)17.6 V10.59 V (44.12%)192.6 WDrop High
25 mm²101 A78 A4.11 V (17.12%)19.9 V6.78 V (28.24%)123.3 WDrop High
35 mm²125 A97 A2.93 V (12.23%)21.1 V4.84 V (20.17%)88.0 WDrop High
50 mm²151 A118 A2.05 V (8.56%)21.9 V3.39 V (14.12%)61.6 WDrop High
70 mm²192 A150 A1.47 V (6.11%)22.5 V2.42 V (10.09%)44.0 WDrop High
95 mm²232 A181 A1.08 V (4.51%)22.9 V1.78 V (7.43%)32.4 W~ ≤5%
120 mm²269 A210 A0.86 V (3.57%)23.1 V1.41 V (5.88%)25.7 W~ ≤5%
150 mm²309 A241 A0.68 V (2.85%)23.3 V1.13 V (4.71%)20.5 W✓ OK (≤3%)
185 mm²353 A275 A0.56 V (2.31%)23.4 V0.92 V (3.82%)16.7 W✓ OK (≤3%)
240 mm²415 A324 A0.43 V (1.78%)23.6 V0.71 V (2.94%)12.8 W✓ OK (≤3%)
300 mm²477 A372 A0.34 V (1.43%)23.7 V0.56 V (2.35%)10.3 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (1.07%)23.7 V0.42 V (1.76%)7.7 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 80 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 80 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 30A over 80m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.