⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 9.77V (2.35%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 9.94V (2.39%)
Voltage at Load405.2 VLine Loss: 5498.2 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1204.64 V (290.28%)0.0 V1987.1 V (478.82%)678112.5 WDrop High
2.5 mm²24 A18 A722.78 V (174.17%)0.0 V1192.26 V (287.29%)406867.5 WDrop High
4 mm²32 A25 A451.74 V (108.85%)0.0 V745.16 V (179.56%)254292.2 WDrop High
6 mm²41 A32 A301.16 V (72.57%)113.8 V496.77 V (119.7%)169528.1 WDrop High
10 mm²57 A44 A180.7 V (43.54%)234.3 V298.06 V (71.82%)101716.9 WDrop High
16 mm²76 A59 A112.94 V (27.21%)302.1 V186.29 V (44.89%)63573.0 WDrop High
25 mm²101 A78 A72.28 V (17.42%)342.7 V119.23 V (28.73%)40686.7 WDrop High
35 mm²125 A97 A51.63 V (12.44%)363.4 V85.16 V (20.52%)29062.0 WDrop High
50 mm²151 A118 A36.14 V (8.71%)378.9 V59.61 V (14.36%)20343.4 WDrop High
70 mm²192 A150 A25.81 V (6.22%)389.2 V42.58 V (10.26%)14531.0 WDrop High
95 mm²232 A181 A19.02 V (4.58%)396.0 V31.38 V (7.56%)10707.0 WDrop High
120 mm²269 A210 A15.06 V (3.63%)399.9 V24.84 V (5.99%)8476.4 WDrop High
150 mm²309 A241 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 WDrop High
185 mm²353 A275 A9.77 V (2.35%)405.2 V16.11 V (3.88%)5498.2 W✓ OK (≤3%)
240 mm²415 A324 A7.53 V (1.81%)407.5 V12.42 V (2.99%)4238.2 W✓ OK (≤3%)
300 mm²477 A372 A6.02 V (1.45%)409.0 V9.94 V (2.39%)3390.6 W✓ OK (≤3%)
400 mm²570 A445 A4.52 V (1.09%)410.5 V7.45 V (1.8%)2542.9 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 150 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 150m at 415V (voltage drop: 9.77V or 2.35%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.