325 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 10.04V (2.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.94V (2.39%)
Voltage at Load405.0 VLine Loss: 5650.9 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1606.19 V (387.03%)0.0 V2649.46 V (638.42%)904150.0 WDrop High
2.5 mm²24 A18 A963.71 V (232.22%)0.0 V1589.68 V (383.05%)542490.0 WDrop High
4 mm²32 A25 A602.32 V (145.14%)0.0 V993.55 V (239.41%)339056.2 WDrop High
6 mm²41 A32 A401.55 V (96.76%)13.5 V662.37 V (159.61%)226037.5 WDrop High
10 mm²57 A44 A240.93 V (58.06%)174.1 V397.42 V (95.76%)135622.5 WDrop High
16 mm²76 A59 A150.58 V (36.28%)264.4 V248.39 V (59.85%)84764.1 WDrop High
25 mm²101 A78 A96.37 V (23.22%)318.6 V158.97 V (38.31%)54249.0 WDrop High
35 mm²125 A97 A68.84 V (16.59%)346.2 V113.55 V (27.36%)38749.3 WDrop High
50 mm²151 A118 A48.19 V (11.61%)366.8 V79.48 V (19.15%)27124.5 WDrop High
70 mm²192 A150 A34.42 V (8.29%)380.6 V56.77 V (13.68%)19374.6 WDrop High
95 mm²232 A181 A25.36 V (6.11%)389.6 V41.83 V (10.08%)14276.1 WDrop High
120 mm²269 A210 A20.08 V (4.84%)394.9 V33.12 V (7.98%)11301.9 WDrop High
150 mm²309 A241 A16.06 V (3.87%)398.9 V26.49 V (6.38%)9041.5 WDrop High
185 mm²353 A275 A13.02 V (3.14%)402.0 V21.48 V (5.18%)7330.9 W~ ≤5%
240 mm²415 A324 A10.04 V (2.42%)405.0 V16.56 V (3.99%)5650.9 W✓ OK (≤3%)
300 mm²477 A372 A8.03 V (1.94%)407.0 V13.25 V (3.19%)4520.8 W✓ OK (≤3%)
400 mm²570 A445 A6.02 V (1.45%)409.0 V9.94 V (2.39%)3390.6 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 200 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 325A over 200m at 415V (voltage drop: 10.04V or 2.42%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.