325 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)7× 400 mm²Drop: 1.24V (2.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.34V (29.88%)
Voltage at Load46.8 VLine Loss: 403.6 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2318.33 V (4829.86%)0.0 V3824.17 V (7967.01%)753458.3 WDrop High
2.5 mm²24 A18 A1391.0 V (2897.92%)0.0 V2294.5 V (4780.21%)452075.0 WDrop High
4 mm²32 A25 A869.37 V (1811.2%)0.0 V1434.06 V (2987.63%)282546.9 WDrop High
6 mm²41 A32 A579.58 V (1207.47%)0.0 V956.04 V (1991.75%)188364.6 WDrop High
10 mm²57 A44 A347.75 V (724.48%)0.0 V573.62 V (1195.05%)113018.7 WDrop High
16 mm²76 A59 A217.34 V (452.8%)0.0 V358.52 V (746.91%)70636.7 WDrop High
25 mm²101 A78 A139.1 V (289.79%)0.0 V229.45 V (478.02%)45207.5 WDrop High
35 mm²125 A97 A99.36 V (206.99%)0.0 V163.89 V (341.44%)32291.1 WDrop High
50 mm²151 A118 A69.55 V (144.9%)0.0 V114.72 V (239.01%)22603.8 WDrop High
70 mm²192 A150 A49.68 V (103.5%)0.0 V81.95 V (170.72%)16145.5 WDrop High
95 mm²232 A181 A36.61 V (76.26%)11.4 V60.38 V (125.79%)11896.7 WDrop High
120 mm²269 A210 A28.98 V (60.37%)19.0 V47.8 V (99.59%)9418.2 WDrop High
150 mm²309 A241 A23.18 V (48.3%)24.8 V38.24 V (79.67%)7534.6 WDrop High
185 mm²353 A275 A18.8 V (39.16%)29.2 V31.01 V (64.6%)6109.1 WDrop High
240 mm²415 A324 A14.49 V (30.19%)33.5 V23.9 V (49.79%)4709.1 WDrop High
300 mm²477 A372 A11.59 V (24.15%)36.4 V19.12 V (39.84%)3767.3 WDrop High
400 mm²570 A445 A8.69 V (18.11%)39.3 V14.34 V (29.88%)2825.5 WDrop High

FAQ — 325 Amp Cable Size at 250 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 250 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 7× 400 mm² copper cable for 325A over 250m at 48V (voltage drop: 1.24V or 2.59%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.