325 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 30 m (98.4 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.52V (2.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.72V (7.17%)
Voltage at Load23.5 VLine Loss: 169.6 W
Max Power & Breaker7.8 kW350A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 30m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 278.2 V (1159.17%) | 0.0 V | 458.9 V (1912.08%) | 90415.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 166.92 V (695.5%) | 0.0 V | 275.34 V (1147.25%) | 54249.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 104.33 V (434.69%) | 0.0 V | 172.09 V (717.03%) | 33905.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 69.55 V (289.79%) | 0.0 V | 114.72 V (478.02%) | 22603.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 41.73 V (173.88%) | 0.0 V | 68.83 V (286.81%) | 13562.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 26.08 V (108.67%) | 0.0 V | 43.02 V (179.26%) | 8476.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 16.69 V (69.55%) | 7.3 V | 27.53 V (114.72%) | 5424.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 11.92 V (49.68%) | 12.1 V | 19.67 V (81.95%) | 3874.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 8.35 V (34.77%) | 15.7 V | 13.77 V (57.36%) | 2712.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 5.96 V (24.84%) | 18.0 V | 9.83 V (40.97%) | 1937.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 4.39 V (18.3%) | 19.6 V | 7.25 V (30.19%) | 1427.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 3.48 V (14.49%) | 20.5 V | 5.74 V (23.9%) | 1130.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.78 V (11.59%) | 21.2 V | 4.59 V (19.12%) | 904.1 W | Drop High |
| 185 mm² | 353 A | 275 A | 2.26 V (9.4%) | 21.7 V | 3.72 V (15.5%) | 733.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.74 V (7.24%) | 22.3 V | 2.87 V (11.95%) | 565.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.39 V (5.8%) | 22.6 V | 2.29 V (9.56%) | 452.1 W | Drop High |
| 400 mm² | 570 A | 445 A | 1.04 V (4.35%) | 23.0 V | 1.72 V (7.17%) | 339.1 W | ~ ≤5% |
FAQ — 325 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 325A at 30 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 30m at 24V (voltage drop: 0.52V or 2.17%).
What is the power capacity of 325A at 24V?
At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.
Related Lengths & Currents (24V)
325A · 5m (24V)325A · 10m (24V)325A · 15m (24V)325A · 20m (24V)325A · 25m (24V)325A · 35m (24V)325A · 40m (24V)325A · 45m (24V)325A · 50m (24V)325A · 60m (24V)325A · 70m (24V)10A · 30m (24V)16A · 30m (24V)20A · 30m (24V)25A · 30m (24V)32A · 30m (24V)40A · 30m (24V)50A · 30m (24V)63A · 30m (24V)80A · 30m (24V)100A · 30m (24V)125A · 30m (24V)160A · 30m (24V)200A · 30m (24V)