325 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.7V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.86V (3.59%)
Voltage at Load23.3 VLine Loss: 226.0 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A139.1 V (579.58%)0.0 V229.45 V (956.04%)45207.5 WDrop High
2.5 mm²24 A18 A83.46 V (347.75%)0.0 V137.67 V (573.62%)27124.5 WDrop High
4 mm²32 A25 A52.16 V (217.34%)0.0 V86.04 V (358.52%)16952.8 WDrop High
6 mm²41 A32 A34.77 V (144.9%)0.0 V57.36 V (239.01%)11301.9 WDrop High
10 mm²57 A44 A20.87 V (86.94%)3.1 V34.42 V (143.41%)6781.1 WDrop High
16 mm²76 A59 A13.04 V (54.34%)11.0 V21.51 V (89.63%)4238.2 WDrop High
25 mm²101 A78 A8.35 V (34.77%)15.7 V13.77 V (57.36%)2712.5 WDrop High
35 mm²125 A97 A5.96 V (24.84%)18.0 V9.83 V (40.97%)1937.5 WDrop High
50 mm²151 A118 A4.17 V (17.39%)19.8 V6.88 V (28.68%)1356.2 WDrop High
70 mm²192 A150 A2.98 V (12.42%)21.0 V4.92 V (20.49%)968.7 WDrop High
95 mm²232 A181 A2.2 V (9.15%)21.8 V3.62 V (15.1%)713.8 WDrop High
120 mm²269 A210 A1.74 V (7.24%)22.3 V2.87 V (11.95%)565.1 WDrop High
150 mm²309 A241 A1.39 V (5.8%)22.6 V2.29 V (9.56%)452.1 WDrop High
185 mm²353 A275 A1.13 V (4.7%)22.9 V1.86 V (7.75%)366.5 W~ ≤5%
240 mm²415 A324 A0.87 V (3.62%)23.1 V1.43 V (5.98%)282.5 W~ ≤5%
300 mm²477 A372 A0.7 V (2.9%)23.3 V1.15 V (4.78%)226.0 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (2.17%)23.5 V0.86 V (3.59%)169.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 15 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 15 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 325A over 15m at 24V (voltage drop: 0.7V or 2.9%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.