325 Amp Cable Size at 40 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.69V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.29V (9.56%)
Voltage at Load23.3 VLine Loss: 226.1 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A370.93 V (1545.56%)0.0 V611.87 V (2549.44%)120553.3 WDrop High
2.5 mm²24 A18 A222.56 V (927.33%)0.0 V367.12 V (1529.67%)72332.0 WDrop High
4 mm²32 A25 A139.1 V (579.58%)0.0 V229.45 V (956.04%)45207.5 WDrop High
6 mm²41 A32 A92.73 V (386.39%)0.0 V152.97 V (637.36%)30138.3 WDrop High
10 mm²57 A44 A55.64 V (231.83%)0.0 V91.78 V (382.42%)18083.0 WDrop High
16 mm²76 A59 A34.77 V (144.9%)0.0 V57.36 V (239.01%)11301.9 WDrop High
25 mm²101 A78 A22.26 V (92.73%)1.7 V36.71 V (152.97%)7233.2 WDrop High
35 mm²125 A97 A15.9 V (66.24%)8.1 V26.22 V (109.26%)5166.6 WDrop High
50 mm²151 A118 A11.13 V (46.37%)12.9 V18.36 V (76.48%)3616.6 WDrop High
70 mm²192 A150 A7.95 V (33.12%)16.1 V13.11 V (54.63%)2583.3 WDrop High
95 mm²232 A181 A5.86 V (24.4%)18.1 V9.66 V (40.25%)1903.5 WDrop High
120 mm²269 A210 A4.64 V (19.32%)19.4 V7.65 V (31.87%)1506.9 WDrop High
150 mm²309 A241 A3.71 V (15.46%)20.3 V6.12 V (25.49%)1205.5 WDrop High
185 mm²353 A275 A3.01 V (12.53%)21.0 V4.96 V (20.67%)977.5 WDrop High
240 mm²415 A324 A2.32 V (9.66%)21.7 V3.82 V (15.93%)753.5 WDrop High
300 mm²477 A372 A1.85 V (7.73%)22.1 V3.06 V (12.75%)602.8 WDrop High
400 mm²570 A445 A1.39 V (5.8%)22.6 V2.29 V (9.56%)452.1 WDrop High

FAQ — 325 Amp Cable Size at 40 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 40 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 325A over 40m at 24V (voltage drop: 0.69V or 2.9%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.