325 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.7V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.15V (4.78%)
Voltage at Load23.3 VLine Loss: 226.0 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A185.47 V (772.78%)0.0 V305.93 V (1274.72%)60276.7 WDrop High
2.5 mm²24 A18 A111.28 V (463.67%)0.0 V183.56 V (764.83%)36166.0 WDrop High
4 mm²32 A25 A69.55 V (289.79%)0.0 V114.72 V (478.02%)22603.8 WDrop High
6 mm²41 A32 A46.37 V (193.19%)0.0 V76.48 V (318.68%)15069.2 WDrop High
10 mm²57 A44 A27.82 V (115.92%)0.0 V45.89 V (191.21%)9041.5 WDrop High
16 mm²76 A59 A17.39 V (72.45%)6.6 V28.68 V (119.51%)5650.9 WDrop High
25 mm²101 A78 A11.13 V (46.37%)12.9 V18.36 V (76.48%)3616.6 WDrop High
35 mm²125 A97 A7.95 V (33.12%)16.1 V13.11 V (54.63%)2583.3 WDrop High
50 mm²151 A118 A5.56 V (23.18%)18.4 V9.18 V (38.24%)1808.3 WDrop High
70 mm²192 A150 A3.97 V (16.56%)20.0 V6.56 V (27.32%)1291.6 WDrop High
95 mm²232 A181 A2.93 V (12.2%)21.1 V4.83 V (20.13%)951.7 WDrop High
120 mm²269 A210 A2.32 V (9.66%)21.7 V3.82 V (15.93%)753.5 WDrop High
150 mm²309 A241 A1.85 V (7.73%)22.1 V3.06 V (12.75%)602.8 WDrop High
185 mm²353 A275 A1.5 V (6.27%)22.5 V2.48 V (10.34%)488.7 WDrop High
240 mm²415 A324 A1.16 V (4.83%)22.8 V1.91 V (7.97%)376.7 W~ ≤5%
300 mm²477 A372 A0.93 V (3.86%)23.1 V1.53 V (6.37%)301.4 W~ ≤5%
400 mm²570 A445 A0.7 V (2.9%)23.3 V1.15 V (4.78%)226.0 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 20 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 325A over 20m at 24V (voltage drop: 0.7V or 2.9%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.