325 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 0.58V (2.41%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.87V (11.95%)
Voltage at Load23.4 VLine Loss: 188.4 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A463.67 V (1931.94%)0.0 V764.83 V (3186.81%)150691.7 WDrop High
2.5 mm²24 A18 A278.2 V (1159.17%)0.0 V458.9 V (1912.08%)90415.0 WDrop High
4 mm²32 A25 A173.87 V (724.48%)0.0 V286.81 V (1195.05%)56509.4 WDrop High
6 mm²41 A32 A115.92 V (482.99%)0.0 V191.21 V (796.7%)37672.9 WDrop High
10 mm²57 A44 A69.55 V (289.79%)0.0 V114.72 V (478.02%)22603.7 WDrop High
16 mm²76 A59 A43.47 V (181.12%)0.0 V71.7 V (298.76%)14127.3 WDrop High
25 mm²101 A78 A27.82 V (115.92%)0.0 V45.89 V (191.21%)9041.5 WDrop High
35 mm²125 A97 A19.87 V (82.8%)4.1 V32.78 V (136.58%)6458.2 WDrop High
50 mm²151 A118 A13.91 V (57.96%)10.1 V22.95 V (95.6%)4520.7 WDrop High
70 mm²192 A150 A9.94 V (41.4%)14.1 V16.39 V (68.29%)3229.1 WDrop High
95 mm²232 A181 A7.32 V (30.5%)16.7 V12.08 V (50.32%)2379.3 WDrop High
120 mm²269 A210 A5.8 V (24.15%)18.2 V9.56 V (39.84%)1883.6 WDrop High
150 mm²309 A241 A4.64 V (19.32%)19.4 V7.65 V (31.87%)1506.9 WDrop High
185 mm²353 A275 A3.76 V (15.66%)20.2 V6.2 V (25.84%)1221.8 WDrop High
240 mm²415 A324 A2.9 V (12.07%)21.1 V4.78 V (19.92%)941.8 WDrop High
300 mm²477 A372 A2.32 V (9.66%)21.7 V3.82 V (15.93%)753.5 WDrop High
400 mm²570 A445 A1.74 V (7.24%)22.3 V2.87 V (11.95%)565.1 WDrop High

FAQ — 325 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 50 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 325A over 50m at 24V (voltage drop: 0.58V or 2.41%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.