⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.38V (1.57%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.38V (1.59%)
Voltage at Load23.6 VLine Loss: 122.2 W
Max Power & Breaker7.8 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A46.37 V (193.19%)0.0 V76.48 V (318.68%)15069.2 WDrop High
2.5 mm²24 A18 A27.82 V (115.92%)0.0 V45.89 V (191.21%)9041.5 WDrop High
4 mm²32 A25 A17.39 V (72.45%)6.6 V28.68 V (119.51%)5650.9 WDrop High
6 mm²41 A32 A11.59 V (48.3%)12.4 V19.12 V (79.67%)3767.3 WDrop High
10 mm²57 A44 A6.96 V (28.98%)17.0 V11.47 V (47.8%)2260.4 WDrop High
16 mm²76 A59 A4.35 V (18.11%)19.7 V7.17 V (29.88%)1412.7 WDrop High
25 mm²101 A78 A2.78 V (11.59%)21.2 V4.59 V (19.12%)904.1 WDrop High
35 mm²125 A97 A1.99 V (8.28%)22.0 V3.28 V (13.66%)645.8 WDrop High
50 mm²151 A118 A1.39 V (5.8%)22.6 V2.29 V (9.56%)452.1 WDrop High
70 mm²192 A150 A0.99 V (4.14%)23.0 V1.64 V (6.83%)322.9 WDrop High
95 mm²232 A181 A0.73 V (3.05%)23.3 V1.21 V (5.03%)237.9 WDrop High
120 mm²269 A210 A0.58 V (2.41%)23.4 V0.96 V (3.98%)188.4 WDrop High
150 mm²309 A241 A0.46 V (1.93%)23.5 V0.76 V (3.19%)150.7 WDrop High
185 mm²353 A275 A0.38 V (1.57%)23.6 V0.62 V (2.58%)122.2 W✓ OK (≤3%)
240 mm²415 A324 A0.29 V (1.21%)23.7 V0.48 V (1.99%)94.2 W✓ OK (≤3%)
300 mm²477 A372 A0.23 V (0.97%)23.8 V0.38 V (1.59%)75.3 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.72%)23.8 V0.29 V (1.2%)56.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 325A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 5m at 24V (voltage drop: 0.38V or 1.57%).

What is the power capacity of 325A at 24V?

At unity power factor, 325A at 24V supports 7.8 kW with a standard 350A circuit breaker.